Manual NOVOS und thanos EVO
Seite
24
Thermokon Sensortechnik GmbH
5.4
Data block “Shading”
Parameter
Description
N3
N5
N7
Touch/
EVO
Min
Max
Default
Access
Data
address
Shading status 1
Depending on the configuration in
register 1616, the action of the user is
performed.
Details in Register 1616.
0..100 = Position of the Blind
(0= max. Down, 100 = max. Up)
110 = Button_No_Press
111 = Button_Short_Press_UP
112 = Button_Long_Press_UP
113 = Button_Short_Press_DOWN
114 = Button_Long_Press_DOWN
115 = Button_Pressed_UP
116 = Button_Pressed_DOWN
●
●
0
116
0
r / w
uint16_t
300
Slat adjustment Blind 1
Angle adjustment of the slats
-180..180 °
●
●
-180
180
0
r / w
uint16_t
301
Shading status 2
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
302
Slat adjustment Blind 2
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
303
Shading status3
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
304
Slat adjustment Blind 3
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
305
Shading status 4
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
306
Slat adjustment Blind 4
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
307
Shading status 5
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
308
Slat adjustment Blind 5
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
309
Shading status 6
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
310
Slat adjustment Blind 6
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
311
Shading status 7
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
312
Slat adjustment Blind 7
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
313
Shading status 8
Description see Shading status 1
●
●
0
116
0
r / w
uint16_t
314
Slat adjustment Blind 8
Description see Slat adjustment 1
●
●
-180
180
0
r / w
uint16_t
315
AUTO Mode
for Shading 1-8
Summary of coils 40-47
If individual shading circuits are to be
controlled temporarily exclusively by the
BMS, the buttons for setting individual
shading circuits can be disabled.
All the buttons on the user interface are
greyed out.
Shading 1-8 (binary coded)
bit 0 = Buttons Shading 1
bit 1 = Buttons Shading 2
…
bit 7 = Buttons Shading 8
0 = AUTO-Mode OFF
1 = AUTO-Mode ON (Buttons locked)
●
●
0
255
0
r / w
uint16_t
316