TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Table 6. TROUBLE-SHOOTING TABLE
Cause
Solution
Installation damage
Due to unsealed connections
Install the connecting piping strain-free to the boiler connections.
Due to freezing
If the heating installation, including the piping network, has not been
built frost-proof, we recommend that you fill the heating installation
with a liquid which has low freezing point and corrosion protection and
antifreeze agent.
Boiler water too hot, heating bodies too cold
1. Hydraulic resistance is too high.
2. Air in the system
3. Inoperable circulation pump
Make sure the circulation pump has been properly selected and the
heating installation is of the proper dimensions. (You must contact your
installer.)
The STB safety thermostat has been
triggered.
Upon reaching a temperature of 95°С, the thermostatic safety protection
device is triggered and the fan is turned off. To resume protection,
remove the black cap on the front panel of the boiler and press the
button on the STB-thermostat. Contact your installer to determine the
cause of protection triggering.
Low boiler temperature.
Unable to reach normal temperature mode of 65°-85° С
Inadequate sizing and/or
combination of heating appliances
Immediately consult your installer about the problem.
Ejection of unburned pellets into the combustion chamber of the boiler
Poor adjustment of the fuel-to-air
ratio from the burner controller
Contact your installer. It is necessary to set the burner properly using
gas analyzer
Utilization of low-quality pellets
Use only fuel which meets the requirements specified in the manual.
(see section 3. Fuel)
Formation of clinkers and noncombustible inclusions inside burner body
Utilization of low-quality pellets (see
section 3. Fuel)
Use only fuel which meets the requirements specified in the manual.
Low performance of the automatic
cleaning system
Increase turn-on frequency of the automatic cleaning system.
Improper setting of fuel-air mixture
Adjust using gas analyzer
Smoke in the pellet hopper
Poor chimney draught or high
internal resistance of the boiler
combustion chamber
Immediately consult your installer about the problem.
Blockage of burner combustion
chamber due to build-up of
noncombustible materials
It is necessary to clean the burner combustion chamber using brush
Improper setting of fuel-air mixture
Adjust using gas analyzer
Dust on the photosensor
It is necessary to clean the photosensor. Refer to the manual for the
cleaning procedure.
Boiler temperature too high. Controller failure.
Grid power fluctuations
It is mandatory to assure a backup power generator of corresponding
rated power! (see table 1)
Power failure
High temperature of exhaust gases.
High temperature alarm is turning
on
Fume exhaust tubes of boiler water jacket are clogged with soot.
Reduced heat transfer. The boiler should be cleaned. Please contact an
authorized specialist / service shop to clean the boiler.
High temperature in boiler water
jacket and low temperature in the
buffer tank.
1. Incorrect ON/OFF temperature settings of pumps.
2. Incorrect sizing of heating system.
Summary of Contents for EN-B
Page 59: ...59 Diagrams Schemes Sch mas 1 3 2 4 5...
Page 60: ...60 Diagrams Schemes Sch mas 5 1 6 45o...
Page 64: ...64 Diagrams Schemes Sch mas 9 10 CHPUMP RT room thermostat TTOP TBOTTOM CHPUMP...
Page 65: ...65 Diagrams Schemes Sch mas 11 T TOP T BOTTOM CHPUMP DHW sensor CHPUMP DHWPUMP TTOP TBOTTOM 12...
Page 66: ...66 Diagrams Schemes Sch mas 23 23 1 U H D V W1 Z O F P M W2 D K W F P L J B L A N B...