The E-Pi Plug-In Module
Cleaning & Repair
Thermo Fisher Scientific
STD5000 & STD6000 User Guide
4-5
6.
Use the contact cleaner to spray off both sides of the membrane. Allow
the cleaner to air dry. Place the membrane on the E-Pi base (membrane
top “T” side up).
7.
Use the contact cleaner to spray off the top, and allow to air dry.
8.
Reassemble the E-Pi, applying downward pressure to the top of the
module while tightening the three set screws.
Figure 4–4.