Troubleshooting & Support
Replacing the CCB
Replacing the CCB
Caution
If this procedure is performed in the field, ensure no contaminates
enter the unit.
▲
1.
Refer to Figure 6–1. Cut off the air supply.
2.
Remove the cover. Remove the E-Pi according to
“Replacing the E-Pi.”
3.
Disconnect the input leads.
4.
Remove the four screws holding the CCB in the manifold.
Note
The replacement CCB should have an O-ring around the pressure
sensor mounted to the CCB. Another O-ring is in the recessed hole where
the pressure sensor plugs in. Do not discard.
▲
5.
Mount the new CCB by reversing these steps.
Figure 6–1.
CCB assembly
6-2
STD5000 & STD6000 User Guide
Thermo Fisher Scientific