background image

Thermo Scientific

 7-1

7

Communication Option

The Communication Option enables digital communication between the UP150 or 

UP550 controller and a PC. It is a factory-installed temperature controller and 

cable assembly using an RS-485 connection through a DB9 cable.

This option is supplied with the necessary cable and diagnostic software to set up 

and check the connections between the unit and the PC. Follow the steps below to 

make the cable connections and to check the data transfer. If you have purchased 

the "SpecView Plus Communication Software" with the copy protection key, refer 

to the SpecView instructions in parallel with this setup outline.

Cable Installation

1. To install the 25-foot external cable, disconnect the electrical power from both 

the unit and PC.

2. Connect the cable end with a black housing to the 9-pin port on the rear of the 

Thermo Fisher Scientific unit.

3. Connect the other cable end with the RS-232/485 Convener to the COM 1 Port 

(or other COM port of your choice) on the rear of the PC.

4. If you have purchased the SpecView Plus Communication Software with the 

copy protection key. Install this key on your parallel port. It may be necessary 

to locate the key between a cable and the parallel port.

5. Apply electrical power to the unit and the PC.

UT550 Communications Setup Parameters

Table 4 shows the default values for UP150 or UP550 Communications Setup 

Parameters. To access these parameters:

1. Hold the SET/ENT button for three second to display the Operating 

Parameters. Press and release the SET/ENT button to display the "LoC" 

parameter. Assure lower value at "ø". Press the down arrow to show "-1" in the 

lower display and press SET/ENT to acknowledge and enter the Setup 

Parameters menu.

2. Press and release the SET/ENT button to access the six parameters specific to 

the communications option.

Summary of Contents for BF51634BC-1

Page 1: ......

Page 2: ...54 USA Thermo Fisher Scientific Inc provides this document to its customers with a product purchase to use in the product operation This document is copyright protected and any reproduction of the who...

Page 3: ...onstruction 2 4 Furnace Insulation 2 4 Thyristor Power Controller 2 4 Chapter 3 Pre Installation Unpacking 3 1 Furnace Assembly 3 1 Chapter 4 Installation Location 4 1 Power Wiring 4 1 Final Inspectio...

Page 4: ...lay 8 1 Excess Temperature Option Feature 8 1 Operating Parameters 8 2 Excess Temperature Controller Operation 8 2 Chapter 9 Maintenance Circuit Breakers 9 2 Heating Element Replacement 9 2 Removing t...

Page 5: ...4 2 Figure 3 Power Connections 4 3 Figure 4 UP150 Control Panel 6 1 Figure 5 Heating Element Repalcement 9 3 Figure 6 Door Insulation Replacement 9 7 Figure 7 Thermocouple Replacement 9 8 Figure 8 Wir...

Page 6: ...List of Figures ii Thermo Scientific...

Page 7: ...giene guidelines and the corresponding technical rules issued by the operator shall be used to create written procedures targeted at personnel working with the subject matter device detailing The deco...

Page 8: ...lure to do so could result in death or serious injury to the user or bystanders and damage to the equipment and any load inside or property nearby This precaution warms of immediate hazards which will...

Page 9: ...his equipment Failure to comply with this precaution could result in damage to equipment used or the furnace and may create an overheat situation Also do not use anything other than OEM exact replacem...

Page 10: ...ing precautions will minimize airborne dust and fiber Keep personnel not involved in the installation out of the area Use a good vacuum to clean area and equipment Use a dust suppressant if sweeping i...

Page 11: ...Fisher Scientific warrants the operational safety and functions of the Laboratory Box Furnaces only under the condition that The Laboratory Box is operated and serviced exclusively in accordance with...

Page 12: ...ratory animals Flammability Non Combustible Reactivity Stable Ingestion May cause gastrointestinal disturbances such as irritation nausea vomiting and diarrhea Eyes Slightly to moderately irritating A...

Page 13: ...ts exposed to doses corresponding to 200 f cc developed progressive lung damage interstitial fibrosis and cancers of the lung and of the pleura lining of the chest wall and lung Hamsters similarly exp...

Page 14: ...its listed in the Ingredients Health Hazard Information section Use NIOSH or MSHA approved equipment when airborne exposure limits are exceeded Acceptable respirators rec ommended for various repairab...

Page 15: ...tion of use Incom patible with strong acids and alkalies Hazardous Decomposi tion and By products None Spill or Release to the Environment Vacuum clean dust where possible Use a dust suppres sant if s...

Page 16: ...airborne exposure limits may be exceeded especially in confined areas with inadequate ventilation Insulation surfaces should be lightly sprayed with H2O before removal to suppress airborne dust As wat...

Page 17: ...re Product This product contains refractory ceramic fibers which have been identified by the International Agency for Research on Cancer IARC as possibly carcinogenic to humans Avoid breathing fiber p...

Page 18: ...INFORMATION AND HANDLING INSTRUCTIONS REX ROTD CORPORATION P O BOX 980 FOWLERVILlE MI 48836 517 223 3787 Explanation of Safety Information and Symbols Safety Notes and Symbols Used Throughout These Op...

Page 19: ...rds and Directives The Box Furnaces complies with the following standards and guidelines Current Approved Agency standards Underwriters Laboratory CSA CE Wear safety gloves Wear safety goggles Harmful...

Page 20: ...Safety Notes Standards and Directives 1 14 Thermo Scientific...

Page 21: ...ssembly consists of the box furnace and a control panel featuring a digital display controller a power module and a single circuit breaker for the furnace heating system Refer to T able 1 for specific...

Page 22: ...with ammeter circuit breaker transformer and front panel indicators for open element fuse failure and power on Type B thermocouples ensure accurate high temperature measurement and long thermocouple...

Page 23: ...does not illuminate in this condition Redundant over temperature controller option B provides positive protection for both furnace and the load ill the event of a control circuit failure This option...

Page 24: ...opened Furnace Insulation The Thyristor Power Controller has been adjusted at the factory for the maximum designed power rating of your furnace model The factory settings are not user adjustable The...

Page 25: ...Assembly The furnace is shipped completely assembled with all heating elements and the thermocouple installed Power connection wires to the furnace are not provided Inspect the furnace as follows 1 C...

Page 26: ...he U hot section of each element is located approximately 1 2 inch from the inside surface of each side chamber wall To adjust a heating element a Hold the terminal end of the element b Apply even pre...

Page 27: ...is manual The 1700 C Box Furnaces are designed for operation on apower source of either 240 or 208 volts single phase at 50 or 60 Hertz If operating on 208 volts change the wiring on the transformer f...

Page 28: ...re 2 Furnace Rear Access 1 Remove the screws fastening the lower rear access panel to the furnace back Save the screws for later use 2 Label two lines L1 and L2 and label the ground wire Ground 3 Thre...

Page 29: ...ts to a bare metal surface Always conform to wiring codes 6 Install the rear access panel with the screws removed in Step 1 Wire 1TB L1 L1 L2 L2 1TB is located include the back of the furnace and on t...

Page 30: ...rol including inside the furnace 2 Check that the door insulation plug refer toFigure Laboratory Box Furnaces aligns with the furnace vestibule opening This plug is designed to reduce heat loss 3 Insp...

Page 31: ...to insert and remove furnace load Do not allow the load to touch the furnace walls Always use a hearth plate on the furnace bottom This furnace should not be left unattended during the Initial break...

Page 32: ...Turn the control circuit breaker on Depending on the specific constructions and there settings The red light on the control panel may illuminate and power may be applied to the elements Always wear t...

Page 33: ...point temperature and if all Controls and indications are working the furnace is ready for use Furnace Operation It is not necessary to repeat the procedure in Section Initial Startup Procedure start...

Page 34: ...ent 2 Turn the control circuit breaker off 3 When the furnace is cool shut of power at the main power disconnect switch To avoid nuisance alarms always change the alarm set point before changing the f...

Page 35: ...UP550 temperature controller is a microprocessor based PID type controller that can store up to 30 programs programs are also referred to as patterns with up to 99 segments each or a single program o...

Page 36: ...s in the Automatic mode Return to Automatic mode by pressing the MODE key until MODE AUTO appears with the flashing word changing Press the SETIENT key When entering and exiting the manual mode the fo...

Page 37: ...tarting setpoint for the pattern and it is typically set at ambient temperature 7 Press SET ENT and STC 0 will appear which stands for start code Leave this setting at 0 8 Press SET ENT and TSP1 value...

Page 38: ...up and down arrow keys to entera setpoint Press the SET ENT key to register the setpoint 4 While in the local mode it is recommended to enter an alarm value The alarm value should be approximately 10...

Page 39: ...sing to the 9 pin port on the rear of the Thermo Fisher Scientific unit 3 Connect the other cable end with the RS 232 485 Convener to the COM 1 Port or other COM port of your choice on the rear of the...

Page 40: ...another 20 minute segment 4 When the Configuration Found windows opens click on the Test Comms for New Config Button 5 The The Input Required window then opens Enter a new Config Name up to 8 charact...

Page 41: ...r power to the control may have been interrupted 12 On some controllers the decimal point position has been changed from use Yokogawa factory default This will make the SpecView display differ from th...

Page 42: ...guration Mode available through the file drop down while in the Run time Mode select the Variables List icon represented by a page with lines on it 2 Select the controller model number and select Prop...

Page 43: ...ee second advances the dis play to the Operation Parameters Menu While in the Operation Parameters Menu use SET ENT to move from one parameter to next and to register changes you have made in set poin...

Page 44: ...n to the normal display Changing Between Celsius and Fahrenheit The controller is factory set to operatewith degrees Celsius To change the display modes and parameter settings to the Fahrenheit scale...

Page 45: ...The Ramp Rate feature allows the chamber to be heated or cooled at any rate slower than the maximum capability of the unit To fine tune ramp rates you may need to test using loads with similar mass a...

Page 46: ...general purposes but your process can be enhanced through the auto tune feature For a given process temperature and product load auto tuning maximizes the performance of the chamber by operating with...

Page 47: ...dicate that the auto tuning is in progress The length of time for the auto tune varies with the load chamber size and temperature selected The auto tune is completedwhen the regular display ofthe meas...

Page 48: ...Communication Option Auto Tuning the Controller 7 10 Thermo Scientific...

Page 49: ...re incident Pressing and releasing the SET ENT button once again shows the current temperature measured by the controller in the top display this may differ slightly from the main temperature controll...

Page 50: ...Operating Parameters by holding the SET ENT button for three seconds Excess Temperature Controller Operation After the Excess temperature Setpoint and Hysteresis values are selected the controller is...

Page 51: ...peak Exceeded Temperature will be lost In some inspires the OUT indicator is illuminated without a high temperature event In this TRIPPED OUT MODE the power to the heating element is introduced A sou...

Page 52: ...Excess Temperature Option B Models Excess Temperature Controller Operation 8 4 Thermo Scientific...

Page 53: ...area Use a good vacuum to clean area and equipment Do not use compressed air Use NIOSH high efficiently respirator 3M 8710 or equivalent Wear long sleeve clothing gloves hat and eye protection to mini...

Page 54: ...ers are located at the rear of the furnace lower left side Press the switch to reset a circuit breaker Replace any circuit breaker that does not reset One control circuit breaker is located in front o...

Page 55: ...cates an open circuit or a broken heating element 3 Remove the side access panel screws on the side of the furnace containing the broken heating element 4 Loosen the three side access panel screws loc...

Page 56: ...e or more heating element complete the following steps 1 Make sure that the main power is disconnected at the disconnect switch 2 Very carefully unpack the replacement heating element s 3 Carefully re...

Page 57: ...eplacement a Fit a braided strap over the outside circumference of the heating element terminal lead section The strap may require some hand forming for good contact between the terminal and the strap...

Page 58: ...tions will minimize aIrborne dust and fiber Keep personnel not involved in the installation out of the area Use a good vacuum to clean area and equipment Use a dust suppressant if sweeping is necessar...

Page 59: ...iodically check the furnace chamber temperature with a separate thermocouple and instrument to determine the amount of error The appropriate frequency of thermocouple replacement depends upon frequenc...

Page 60: ...leads from the terminal screws on the thermocouple head 3 Lift the thermocouple vertically out of its hole in the top insulation 4 Replace the thermocouple and connectthe new wires Red is always nega...

Page 61: ...ting controller and furnace problem Problem Solution Absence of current and presence of volt age on element input terminal Heating element is cracked or open Replace broken element Heating element cur...

Page 62: ...ent above 995 C to restore coat ing Foreign substance on heating element Furnace temperature is too high Thermocouple a Check the thermocouple visually for breaks If a break is evident replace the the...

Page 63: ...rol circuit breaker is on 2 Check that the red light is working Replace the light If necessary 3 Check that the door interlockswitch has a closed circuit when the door is closed Adjust or replace the...

Page 64: ...Troubleshooting 10 4 Thermo Scientific...

Page 65: ......

Page 66: ......

Page 67: ...BLOCKS SIX WIRES TOTAL 1 PAIR PER FAN TYP TYP 3 FAN 38 3A 3A COOLING FAN POWER ON ILT 4F 3F POWER CIRCUIT 108 109 A 32 108 109 51 60 75 12 1 50 ICB 60A RT POLE LT POLE TERMINAL SIDE OR REAR VIEW 30 IL...

Page 68: ...INDIVIDUAL WIRE CONNECTIONS TO EACH FAN FUSE BLOCKS SIX WIRES TOTAL 1 PAIR PER FAN TYP TYP 3 FAN 38 3A 3A COOLING FAN POWER ON ILT 4F 3F POWER CIRCUIT 108 109 A 32 108 109 51 60 75 12 1 50 ICB 60A RT...

Page 69: ...Thermo Scientific 12 1 12 Error Codes This chapter is not applicable...

Page 70: ...Error Codes 12 2 Thermo Scientific...

Page 71: ...izieren die unter diese RoHS Anweisung fillen finden Sie unter www thermo com WEEERoHS Italia Questo prodotto deve risponderealla direttiva dell unione Europea 2002 96EC in merito ai Rifiuti degli App...

Page 72: ...WEEE Compliance 13 2 Thermo Scientific...

Page 73: ...Thermo Scientific 14 1 14 14 Spare Parts and Accessories This chapter is not applicable...

Page 74: ...Spare Parts and Accessories 14 2 Thermo Scientific...

Page 75: ...Thermo Scientific 15 1 15 Device Log 1700 C Box Furnaces Part number Serial number Service number Location Operator s note Work carried out Notes Date Signed...

Page 76: ...Device Log 15 2 Thermo Scientific...

Page 77: ...112114 Email info labequipment de thermofisher com Enquiries from Europe Middle East and Africa Phone 49 0 6184 90 6940 Fax 49 0 6184 90 6772 E Mail info labequipment de thermofisher com Postal addres...

Page 78: ...Contact 16 2 Thermo Scientific Enquiries from Asia Pacific Phone 852 2711 3910 Fax 852 2711 3858 E Mail info labequipment thermofisher com...

Reviews: