MEB Options
2-D/A MEB
A unique address that determines the software configuration must be set
using jumpers J6 and J7 for each 2-D/A MEB installed. The address
jumpers are configured as shown below.
Table 4–18. Address jumper configuration for 2-D/A MEB
Board #
J6
J7
1
Not installed
Not installed
2
Installed
Not installed
3
Not installed
Installed
4
Installed
Installed
Connect TB2 on the 2-D/A MEB to the MEB terminal block (TB2) on
the enclosure door panel as shown below.
Table 4–19. 2-DA MEB to TB2 connections
Color
TB2 on 2-DA MEB
TB2 on Enclosure Door
Green
TB2-4 (GND)
TB2-6 (GND)
Blue
TB2-3 (+5V)
TB2-3 (VCC)
Yellow
TB2-2 (SDA)
TB2-4 (SDA)
White
TB2-1 (SCL)
TB2-5 (SCL)
The following figure shows typical analog output connections (see
for a detailed wiring diagram, including connection to the
12/24 Vdc converter).
Figure 4–11.
Typical output connections to the 2-D/A MEB
Address Jumpers
Connection to MEB
Terminal Block
Analog Outputs
4-16 AutoPILOT PRO Flow Computer User Guide
Thermo Fisher Scientific