Electrical Maintenance
74
AC Components
Contactors
Test the contact points of the contactor by
checking the voltage drop across each set of
points when the contactor is energized and the
system is operating. If the voltage drop across a
set of points is more than 15 volts ac, replace the
contact points as a set.
Test the contactor coil by checking the voltage
across the coil. The contactor coil should be
energized by a minimum of 10 volts DC.
Overload Relay
The overload relay should open if the motor
circuit current draw is more than 12 amps for
380/460 volt systems or 24 amps for 200/230 volt
systems.
In-Cab TG-V Controller
Multi-Temp In-Cab TG-V
P/N 41-1548 — 12V
P/N 41-1549 — 24V
Figure 28: Multi-Temperature In-Cab TG-V
Controller
The In-Cab TG-V functions similarly to the
standard unit mounted TG-V. However, the
In-Cab TG-V Controller also has the following
additional features:
•
Alarm Codes for Multi-Temperature In-Cab
TG-V
•
Power Cord LED on Model 50 Units
•
Whisper (Low Speed) Push Button
The operating manuals and the setup and
operating manuals contain information about the
control functions and how to customize the
display screens. Manuals for the Multi
Temperature In-Cab TG-V Controller: Operating
Manual (TK 40941) and Operating and Setup
Manual (TK 40805-1).
The same interconnecting harness (P/N 41-346) is
used for the Single Temperature In-Cab TG-V and
the Multi-Temp In-Cab TG-V.
A stand alone tester is available as P/N 204-831. It
will test all In-Cab TG-V Controllers.
Code 88 should be cleared with the tester before
declaring the microprocessor faulty.
CAUTION: The unit uses high voltage
alternating current (ac) during electric
operation. Lethal voltage potentials can
exist on connections in the high voltage
box. Take appropriate precautions and use
extreme care when testing the unit.
Alarm
Code
Fault Condition
03
Condensing Unit Return Air Sensor
Faulty
03A
Remote Unit Return Air Sensor Faulty
14
Condensing Unit Defrost Circuit Failure
25
Battery Charging Alternator Failure
29
Defrost Initiation Failure
47
Remote Unit Defrost Circuit Failure
74
Cold Start or Checksum Error
75
Microprocessor RAM Faulty
76
Microprocessor EEPROM Faulty
77
EPROM Faulty
88
Microprocessor Faulty
Summary of Contents for MD-MT
Page 4: ...4...
Page 10: ...Table of Contents 10...
Page 22: ...Specifications 22...
Page 43: ...Unit Description 43 Figure 15 Engine Side Door Open ARD041...
Page 48: ...Unit Description 48...
Page 128: ...Refrigeration Service Operations 128...
Page 134: ...Hilliard Clutch Maintenance 134...
Page 136: ...Structural Maintenance 136...
Page 148: ...Refrigeration Diagnosis 148...
Page 150: ...Remote Evaporator Specifications 150...
Page 152: ...Remote Evaporator Maintenance Inspection Schedule 152...
Page 156: ...Remote Evaporator Unit Description 156...
Page 160: ...Remote Evaporator Structural Maintenance 160...
Page 162: ...Remote Evaporator System Diagnosis 162...
Page 166: ...Wiring and Schematic Diagrams Index 166...
Page 167: ...167 MD RD MT Model 30 w In Cab Schematic Diagram Page 1 of 2...
Page 168: ...168 MD RD MT Model 30 w In Cab Schematic Diagram Page 2 of 2...
Page 169: ...169 MD RD MT Model 30 w In Cab Wiring Diagram Page 1 of 3...
Page 170: ...170 MD RD MT Model 30 w In Cab Wiring Diagram Page 2 of 3...
Page 171: ...171 MD RD MT Model 30 w In Cab Wiring Diagram Page 3 of 3...
Page 172: ...172 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 173: ...173 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Page 174: ...174 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 175: ...175 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 176: ...176 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 177: ...177 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 178: ...178 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 179: ...179 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 180: ...180 MD RD MT Model 50 w In Cab Schematic Diagram Page 1 of 2...
Page 181: ...181 MD RD MT Model 50 w In Cab Schematic Diagram Page 2 of 2...
Page 182: ...182 MD RD MT Model 50 w In Cab Wiring Diagram Page 1 of 3...
Page 183: ...183 MD RD MT Model 50 w In Cab Wiring Diagram Page 2 of 3...
Page 184: ...184 MD RD MT Model 50 w In Cab Wiring Diagram Page 3 of 3...
Page 185: ...185 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 186: ...186 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Page 187: ...187 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 188: ...188 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 189: ...189 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 190: ...190 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 191: ...191 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 192: ...192 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 3 of 3...