The application programme "thePixa P360 KNX"
Optical presence detector thePixa P360 KNX
36
5.6
Zone related parameters
The detection area can be divided into up to 6 independent zones.
5.6.1
General zone settings
Designation
Values
Description
Zone name (optional)
text field
For easy distinction of zones, e.g.
Office 1.
Designation can be changed later in
the app.
Operating mode
master
The zone controls connected actuators
independently, based on the detection
of motion/presence and possibly the
detection of one or more zone/s in
parallel switching.
slave
The zone is not connected to any
actuator, but only provides detection
information to one or more zones in
"master" operating mode.
Only applies to channels light and
HVAC.
The channel room occupancy is not
affected by this setting.
Master operating mode
individual switching
Zone operates autonomously.
parallel switching
Depending on requirements, additional
zones are linked together as Master or
Slaves for the extension of the
detection range.
Please observe the information on
parallel switching in chapter 7 on page
aura effect (light)
The light follows the user in the area
where he is currently moving. The
lighting in the surrounding zones is
switched or dimmed to the <Switch-on
dimming value at aura>.
Please observe the information on the
aura effect in chapter 8 on page 59.