Apr-08-2016 GI-50 320 DS (NZ308)_UL April 2016
From Step 4
Step 4
CONFIGURING CH3 FUNCTIONS PROCEDURE
Pass Brightness Mode,
Calibration Mode, and
Codes 1 to 4 and enter
Code 5
Set Code 5 to [11X]:
1st Digit = 1 Selects square root of CH3
2nd Digit = 1 Selects voltage, current
3rd Digit = X Not relevant
Save CH3 setting
Exit Code 6.
Return to
Operational Display
To
Step
5
Step 3
Step 1
Step 2
Operational Display
Enter Brightness Mode
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
6
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
at same
time
Press
at same
time
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Step 5
Operational Display
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
OR
Press
at same
time
Press
at same
time
CONFIGURE CH3
FUNCTIONS
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
1
Initial Setup Procedures
[CodE_5] - Channel 3 Functions
0 Direct Display of
Input (no processing)
1
Square Root of
Channel 3
2 Inverse of Channel 3
3
4 kB Meters
32-point Linearization
of CH3 using Table 1
32 kB Meters
32-point Linearization
of CH3 using Table 3
Note:
All linearization
tables are set up in
the Calibration Mode
[24X].
Code 5 is a single code that
combines all the configuration
and post processing functions
available for Channel 3.
When a
triple input
signal con-
ditioner is installed, the third
input signal is processed and
displayed on CH3.
Post processing and measure-
ment task functions for CH3
are configured in the 1st, 2nd,
and 3rd digits of Code 5. The
diagram opposite lists the avail-
able configuration selections in
Code 5.
Example Procedure:
Configure CH3 to display the square root of a
voltage input by setting Code 5 to [
11X
].
FOR THERMOCOUPLE
0 Type J
1 Type K
2 Type R
3 Type S
4 Type T
5 Type B
6 Type N
7 Select user defined lineariza-
tion table (Table 1) set up in CAL
[24X]
FOR RTD TYPE (2-, 3-, 4- WIRE)
0 Resistance
1 RTD 385
2 RTD 392
3 RTD 120
4 Cn 10
MEASUREMENT TASK
0 No Function
1 Voltage / current
2 TC (3rd digit selects type of TC)
3 RTD (3rd digit selects type of RTD)
4 Real Time Clock & Timer (3rd digit selects type)
5 -
6 -
7 Smart Input Module (3rd digit selects register)
CODE 5 – CHANNEL 3 FUNCTIONS
FIRST DIGIT
SECOND DIGIT
THIRD DIGIT
CH3 POST PROCESSING
FOR REAL-TIME CLOCK & TIMER
0 HRS:MIN:SEC
1 HRS:MIN
2 -
3 -
4 1 Second Count UP Timer
5 1 Second Count DOWN Timer
6 -
7 -
FOR SMART INPUT MODULE
0 Output Register 1
1 Output Register 2
2 Output Register 3
3 Output Register 4
4 Output Register 5
5 Output Register 6
6 Output Register 7
7 Smart Input Module Register 2
Code Setup
P
Press
Use the
buttons to set the
required smart input module code
(0 to 377). See
I-Series Input
Module Guide (Z87)
for code
details.
See
I-Series Input Modules Guide (Z87)
for pro-
cedures to set up a triple input module.
START HERE