Operational Display

SETPOINT SETTING  

AND RELAY 

CONFIGURATION MODE

STEP A

STEP B

STEP C

STEP D

No [doM] or [dob]

No [doM] or [dob]

STEP E

STEP F

STEP G

STEP H

STEP I

STEP J

STEP K

STEP L

To Step M of Setpoint

Setting and Relay

Configuration Page 9

The following programming steps are required to enter the setpoint values and configure the relay functions 

in a meter with four relays using four setpoints. Generally if less than four relays are installed, the setpoints 

without relays are operational in software for tri-color control or display only purposes.  To remove unwanted 

setpoint indications, set them to 9999 or -1999 depending on the relay activation mode selected.

STEP A  Enter the Setpoint Mode

 

1)  Press the 

P

 and   

buttons at the same time. Display toggles between [SP1] and the previous 

SP1 setting.

STEP B  Set Setpoint 1 [SP1]

 

1)  Using the   and   

buttons, adjust the display to the desired SP1 value.

 

2)  Press the 

P

 

button. Display toggles between [doM] and the previous [doM] setting.

STEP C  Set the SP1 Delay-on-Make [doM] Delay Time Setting

 1) 

Using the   and   

buttons, adjust the display to the desired [doM] value (0 to 9999 seconds). 

The reading must continuously remain in an alarm condition until this delay time has elapsed before 

the relay will make contact (energize).

 

2)  Press the 

P

 

button. Display toggles between [dob] and the previous [dob] setting.

STEP D  Set the SP1 Delay-on-Break [dob] Delay Time Setting

 1) 

Using the   and   

buttons, adjust the display to the desired [dob] value (0 to 9999 seconds). 

The reading must continuously remain in a non-alarm  condition until this delay time has elapsed 

before the relay will break contact (de-energize).

 

2)  Press the 

P

 

button. Display toggles between [hYSt] and the previous [hYSt] setting.

STEP E  Select the Hysteresis [hYSt]

 1) 

Using the   and   

buttons, select the Hysteresis to be ON or OFF. 

 

2)  Press the 

P

 

button. Display toggles between PUM and (on) or (oFF).

STEP F  Select Pump [PUM] (on) or (oFF)

 1) 

Using the   and   

buttons, select the Pump to be ON or OFF.  When PUM is selected ON, and 

SP2 is set at a value higher than SP1, the SP1 relay will operate in a special "pump on pump off" mode.  

SP2 acts as the upper limit and SP1 acts as the lower limit of the Hysteresis Band on the SP1 relay.

For filling applications: 

[rLYS] should be set to [LhXX] (see step M).  The SP1 relay and SP1 LED Annunciator will then activate for inputs 

less than the SP1 setpoint, and remain ON until the SP2 setpoint is reached.

For emptying applications: 

[rLYS] should be set to [hhXX] (see step M).  The SP1 relay and SP1 LED Annunciator will then activate for inputs 

greater than the SP2 setpoint, and remain ON until the SP1 setpoint is reached.

 

2)  Press the 

P

 

button. Display toggles between [SP2] and the previous SP2 setting.  

 

STEP G  Set Setpoint 2 (SP2)

 

1)  Using the   and   

buttons, adjust the display to the desired SP2 value.

 

2)  Press the 

P

 

button. Display toggles between [hySt] and the previous [hySt] setting.

STEP H  Select the Hysteresis [hYSt]

 1) 

Using the   and   

buttons, select the Hysteresis to be ON or OFF. 

 

2)  Press the 

P

 

button. Display toggles between [SP3] and the previous [SP3] setting.

STEP I  Set Setpoint 3 (SP3) (No [doM] or [dob])

 

1)  Using the   and   

buttons, adjust the display to the desired SP3 value.

 

2)  Press the 

P

 

button. Display toggles between [hySt] and the previous [hySt] setting.

STEP J  Select the Hysteresis [hYSt]

 1) 

Using the   and   

buttons, select the Hysteresis to be ON or OFF. 

 

2)  Press the 

P

 

button. Display toggles between [SP4] and the previous [SP4] setting.

STEP K  Set Setpoint 4 (SP4) (No [doM] or [dob])

 1) 

Using the   and   

buttons, adjust the display to the desired SP4 value.

 

2)  Press the 

P

 

button. Display toggles between [hySt] and the previous [hySt] setting.

STEP L  Select the Hysteresis [hYSt]

 1) 

Using the   and   

buttons, select the Hysteresis to be ON or OFF. 

 

2)  Press the 

P

 

button. Display toggles between [rLYS] and the previous relay setting.

Please Continue On Next Page.

Setpoint Setting and Relay Configuration Mode 

Summary of Contents for CL-B101D40HZ

Page 1: ...Mode Selection 6 Bargraph Color Programming Mode 9 Case Dimensions 13 Component Layout 11 Connector Pinouts and Pin Descriptions 10 11 Controls and Indicators 2 Decimal Point and Brightness Selection...

Page 2: ...irection indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are shown...

Page 3: ...See Page 5 Goes directly to Zero setting if Analog Output is not installed 4 00 20 00 Range 99 99 9999 999 9 Select one of three Ranges 99 99Hz 999 9Hz or 9999Hz PROGRAMMABLE OFFSET AND SCALE FACTOR...

Page 4: ...6 meter may be rescaled without applying an external signal by changing the Offset and Scale factor Offset is the reading that the meter will display for a zero input The Offset may be set to any valu...

Page 5: ...this point the display skips directly to STEP G and toggles between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph...

Page 6: ...h and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Small...

Page 7: ...volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reve...

Page 8: ...ress the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value h...

Page 9: ...argraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color sett...

Page 10: ...mp Form A relays An analog output module is also shown as installed The CL B101D40HZ uses plug in type screw terminal connectors for all input and output connections The power supply connec tions pins...

Page 11: ...A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Main...

Page 12: ...ditioning Modules COUPLING INPUT SIGNAL FILTER MAG NAMUR SOURCE SINK LOAD AC 20KHz 2KHz 200Hz OFF DC MAG AC LOGIC GND 24V INPUT High Accuracy Digital Measurement NPN Open Collector Proximity Switch No...

Page 13: ...t the meter from external noise Input output leads should be routed as far away as possible from contactors control relays transformers and other noisy components Shielding cables for input output lea...

Page 14: ...y 50 POWER SUPPLY PS1 85 265VAC 95 300VDC N C PS2 18 48VAC 10 72VDC 40 INPUT MODULES Partial List See www texmate com Unless otherwise specified Texmate will ship all modules precalibrated with factor...

Reviews: