CL-B101D40HZ Manual (d0098)

Page 3

Software Logic Tree

The 

CL-B101D40HZ

 is an intelligent bargraph meter with a hier-

archical software structure designed for easy programming and 

operation, as shown below in the software logic tree.

v

When power is applied, all segments of the bargraph and 

digital display light up for 3 seconds.  The version number of 

the installed software is then displayed for 2 seconds, after 

which, the operational display indicates the input signal.

15 Second Program Timeout

Except for ZERO and SPAN settings in the Two 

Point Digital Calibration Mode and the Analog 

Output Range Setting and Calibration Mode 

(cLo and chi), the meter has a 15 second  

program timeout. If no buttons are pressed for 

15 seconds in any of the other programming 

sequences, the meter will exit the program-

ming mode and return to the operational 

 

display. Any program changes that were made 

prior to pressing the 

P

 button in the preced-

ing step will not be  saved.

Peak

Reset

PEAK

Reset

VALY

Valley

PEAK & VALLEY 

VIEW & RESET

Operational Display

MAIN  MENU

Bargraph Center Point

Display Selection (cto)

This branch will

only appear if

the analog

output option

is installed

Back to

Operational

Display

Digital Display ON/OFF 

Selection (diSP)

Sub-menu MODE

Calibration Mode

Calibration 

Input

Calibration 

Output

offset

(ZEro)

Scale

Factor

(SPAn)

Calibrate Analog 

Output Lo 

Calibrate Analog 

Output Hi 

Select the Digital

Reading at which

the Analog Output

Hi (chi) will occur

Select the Digital

Reading at which

the Analog Output

Lo (cLo) will occur 

This branch will only

appear, if the analog

output option

is installed

DIGITAL SPAN SELECTION

FOR ANALOG RANGE OUTPUT

See Page 6

DIGITAL DISPLAY ON/OFF

See Page 6

RANGE SELECTION

See Page 7

BARGRAPH CENTER POINT
DISPLAY MODE SELECTION

See Page 6

TWO POINT ANALOG OUTPUT

RANGE SETTING AND CALIBRATION

See Page 7

Set the Decimal

Point (dp)

Bargraph Display

Scale Lo Range

Setting (bLo)

Bargraph Display

Scale hi Range

Setting (bhi)

Display

Brightness (br)

1  Dimmest

2  Dim        

3  Bright     

4  Brightest

[X•XXX]

[XX•XX]

[XXX•X]

[XXXX•]

[XXXX]

DECIMAL POINT AND

BRIGHTNESS SELECTION

See Page 5

DIGITAL SPAN SELECTION

FOR BARGRAPH DISPLAY

See Page 5

Goes directly

to Zero setting

if Analog Output

is not installed

+

4.00

+

20.00

Range

[99•99]

[9999]

[999•9]

Select one of three 

Ranges: 99.99Hz,

999.9Hz or 9999Hz

 PROGRAMMABLE

OFFSET AND

SCALE FACTOR

See Page 4

[orAn]

[rEd]

NOTE: Will only 

appear if a tricolor 

display is installed

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

BARGRAPH COLOR 

PROGRAMMING MODE

See Page 10

Tricolor Bargraph

The tri-color bargraph is designed 

like a traffic light, to display either 

red, orange or green, but only one 

color at a time. The color to be 

displayed is selected in two ways.

The first step is to select the color 

to be displayed when the bar is 

“below” whichever set point is set 

to the lowest position.

The second step is to select the 

color to be displayed when the bar 

is above each specific setpoint, 

regardless of the order or position 

to which the set points are set.

However, if two or more setpoints 

with differently specified colors are 

positioned at the same set point 

value, the color specified for the set 

point with the highest identifying 

number will be displayed. When 

setpoints are set to the same value, 

the SP4 color overrides the SP3 

color, the SP3 color overrides the 

SP2 color, and the SP2 color 

overrides the SP1 color.

SETPOINT SETTING  AND 

RELAY CONFIGURATION MODE

See Page 9

L or h

L or h

L or h

L or h

Relays 

Activation [rLYS]

 

(h) High 

the relay 

energizes 

when the setpoint 

is exceeded

(L) Low 

the relay

energizes below 

the setpoint. 

Pump On Pump Off [PUM]

When PUM is selected on, 

and SP2 is set at a value 

higher than SP1, the SP1 

relay will operate in a special 

"pump on pump off" 

Hysteresis mode.  SP2 acts 

as the upper limit and SP1 

acts as the lower limit of the 

Hysteresis Band.

For filling applications, rLYS 

should be set to LhLh.  SP1 will 

then activate for inputs less than 

the SP1 setpoint, and remain 

ON until the SP2 setpoint is 

reached.

For emptying applications

rLYS should be set to hhhh.  

SP1 will then activate for inputs 

greater than the SP2 setpoint, 

and remain ON until the SP1 

setpoint is reached.

Set Setpoint 1

[SP1]

Delay-on-Make

[doM]

Delay-on-Break

[dob]

Setpoint 2 

[SP2]

NOTE: [dom] [dob] 

Functions are only 

available for SP1 

0 to 9999

seconds

0 to 9999

seconds

Pump

[PUM]

Hysteresis

[hYSt]

Hysteresis

[hYSt]

Hysteresis

[hYSt]

Hysteresis

[hYSt]

Setpoint 3

[SP3]

Setpoint 4

[SP4]

BRIGHTNESS AND

SETPOINT VIEW MODE

1  Dimmest

2  Dim        

3  Bright     

4  Brightest

Summary of Contents for CL-B101D40HZ

Page 1: ...Mode Selection 6 Bargraph Color Programming Mode 9 Case Dimensions 13 Component Layout 11 Connector Pinouts and Pin Descriptions 10 11 Controls and Indicators 2 Decimal Point and Brightness Selection...

Page 2: ...irection indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are shown...

Page 3: ...See Page 5 Goes directly to Zero setting if Analog Output is not installed 4 00 20 00 Range 99 99 9999 999 9 Select one of three Ranges 99 99Hz 999 9Hz or 9999Hz PROGRAMMABLE OFFSET AND SCALE FACTOR...

Page 4: ...6 meter may be rescaled without applying an external signal by changing the Offset and Scale factor Offset is the reading that the meter will display for a zero input The Offset may be set to any valu...

Page 5: ...this point the display skips directly to STEP G and toggles between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph...

Page 6: ...h and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Small...

Page 7: ...volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reve...

Page 8: ...ress the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value h...

Page 9: ...argraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color sett...

Page 10: ...mp Form A relays An analog output module is also shown as installed The CL B101D40HZ uses plug in type screw terminal connectors for all input and output connections The power supply connec tions pins...

Page 11: ...A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Main...

Page 12: ...ditioning Modules COUPLING INPUT SIGNAL FILTER MAG NAMUR SOURCE SINK LOAD AC 20KHz 2KHz 200Hz OFF DC MAG AC LOGIC GND 24V INPUT High Accuracy Digital Measurement NPN Open Collector Proximity Switch No...

Page 13: ...t the meter from external noise Input output leads should be routed as far away as possible from contactors control relays transformers and other noisy components Shielding cables for input output lea...

Page 14: ...y 50 POWER SUPPLY PS1 85 265VAC 95 300VDC N C PS2 18 48VAC 10 72VDC 40 INPUT MODULES Partial List See www texmate com Unless otherwise specified Texmate will ship all modules precalibrated with factor...