51
7-2. Isolated programming and monitoring
◆
Refer to Table 7-1 for detailed description of the rear panel Isolated Programming & Monitoring connector.
To provide the lowest noise performance, it is recommended to use shielded-twisted pair wiring.
◆
Refer to Fig.7-1 for description of the connector.
Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix.
Shield
+VPROG_ISO
+IPROG _ISO
GND
1
2
3
4
5
6
7
8
Shield
+IMON_ISO
+VMON _ISO
GND
Fig.7-1: Isolated Programming & Monitoring connector
Table 7-1: Detailed description of Isolated programming & Monitoring connector
Terminal
Signal name
Function
Range
0V to 5V/0V to 10V
IS510 option
Rang
4mA to 20mA IS420
option
1
SHLD
Shield, connected internally to
chassis of the supply.
Chassis ground
2
+VPROG_ISO
Output voltage programming input
0V to 5V/0V to 10V
4mA to 20mA
3
+IPROG_ISO
Output current programming input
0V to 5V/0V to 10V
4mA to 20mA
4
GND
Ground for programming signals.
Ground
Ground
5
GND
Ground for programming signals.
Ground
Ground
6
+VMON_ISO
Output voltage monitoring output
0V to 5V/0V to10V
4mA to 20mA
7
+IMON_ISO
Output current monitoring output
0V to5V/0V to 10V
4mA to 20mA
8
SHLD
Shield, connected internally to
chassis of the supply.
Chassis ground
CAUTION
!
When the Isolated Analog Option is installed, do not apply any signals to the
non-isolated VPGM and IPGM (J1-9 and J1-10) pins. All other J1 features may be
used normally.
◆
Refer to
"3-4. J1 programming and monitoring connector"
for a description of J1
features.