2
1-4. Output connections
Output connections are made to rear panel bus-bars for models up to 60V and to a 4-terminal wire clamp connector for
models above 60V rated output voltage. Either the positive or negative terminal may be grounded or the output may
be floated. Models up to 60VDC Rated Output shall not float outputs more than
±
60VDC above/below chassis
ground. Models >60VDC Rated Output shall not float outputs more than
±
600VDC above/below chassis ground.
Contact factory for assistance with higher float voltage applications.
Local or remote sense may be used. In remote sense, the voltage drop on the load wires should be minimized.
◆
Refer to the
for the maximum voltage drop value.
1-5. Cooling and mechanical construction
The PU series is cooled by internal fans. At the installation, care must be taken to allow free air flow into the power
supply via the front panel and out of the power supply via the rear panel. The PU power supplies have a compact and
lightweight package which allows easy installation and space saving in the application equipment.
CAUTION
!
Observe all torque guidelines within this manual. Over torque may damage unit or
accessories. Such damage is not covered under manufacturers warranty.
1-6. Models covered by this manual
Table1-1: Models covered by the manual
Model
Voltage range (V)
Current range (A)
Model
Voltage range (V)
Current range (A)
PU6-200
0 to 6
0 to 200
PU60-25
0 to 60
0 to 25
PU8-180
0 to 8
0 to 180
PU80-19
0 to 80
0 to 19
PU12.5-120
0 to 12.5
0 to 120
PU100-15
0 to 100
0 to 15
PU20-76
0 to 20
0 to 76
PU150-10
0 to 150
0 to 10
PU30-50
0 to 30
0 to 50
PU300-5
0 to 300
0 to 5
PU40-38
0 to 40
0 to 38
PU600-2.6
0 to 600
0 to 2.6