deCommIssIonIng
43
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.A.01 Last revised
07/2020
5
Wait 15 minutes until the system is largely voltage-free as the capacitors in the inverter take several
minutes to discharge.
6
Switch off the following circuit breakers
33
in the connector panel
D
in sequence:
1. F7 –> 2. F5 –> 3. F4 –> 4. F3. Information on assigning the circuit breakers can be found in section “5.8
Connector panel” on page 19 et. seq.
7
In the connector panel, remove the 35 A NH00 fuses
9
or
37
(see “5.8 Connector panel” on page 19 et. seq.) for the con-
sumer line from the right fuse holder. Then close the fuse holder.