4 Transmitter
15
• 12 terminals for a total of 4 relays.
If no relays are available, settings for monitoring limit values
or alarms can still be controlled via the display. The alarm
status will be shown on the display.
Only have the transmitter wired and connected by
authorized personnel with the voltage disconnected.
4.2.5.
Analog outputs
As analog outputs, the testo 6383 has either
• 1 current output of 0 to 20 mA (4-wire)/4 to 20 mA (4-wire) or
• 1 voltage output of 0 to 1 V/0 to 5 V/0 to 10 V (4-wire)
4.2.6.
Parameters
The following parameters are displayed:
• Differential pressure in Pa, hPa, kPa, mbar, bar, mmH
2
O,
kg/cm
2
, PSI, inch HG, inch H
2
O
•
4.2.7.
Scaling
There are three types of min./max. values:
1
The measuring range: The maximum sensor performance is in
this range. Values outside of the measuring range are displayed
via messages, for example. Measuring range, see table
(below).
2
Standard scaling: The output signals are assigned to this
measuring range as standard:
◦
during delivery if no entries are made in the order code
◦
after exchanging the unit, the measuring range recorded in
the instrument is applied as standard.
The transmitter even retains its scaling with the voltage
disconnected.
Measuring range, see table (below).
3
The maximum settings for the manual scaling
◦
The maximum limits can be calculated as follows:
X = difference between MIN. and MAX. value of the
standard scaling
(Max. value of standard) + (50 % of X)
(Min. value of standard) - (50 % of X)
◦
It is thus possible to scale beyond the measuring range, e.g.
for the adjustment of the scaling limits to standard values of
a PLC.
Summary of Contents for 6383
Page 2: ...2 ...
Page 12: ...4 Transmitter 12 4 1 5 Dimensions ...
Page 39: ...4 Transmitter 39 4 4 4 Overview of the testo 6383 user menu ...
Page 40: ...4 Transmitter 40 ...
Page 87: ...6 Tips and assistance 87 ...