28
WARNING !!! :
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent disturbances.
WARNING !!! :
External battery cables must be shielded.
NOTE :
Output cables must be shorter than 10 meters.
UPS
RATING
(kVA)
NOMINAL CURRENT : Amps / Recommended Cable Size (mm
2
)
BUS BAR CONNECTION
STUD SIZE
Input Mains
With full battery Recharge
Bypass / output
At full load
Battery
at min.
Battery
Voltage
Input/Output
Cable
Terminations
U-V-W-N
Battery
Terminations
+ & -
380V
400V
415V
380V
400V
415V
A / mm
2
A / mm
2
A / mm
2
A / mm
2
A / mm
2
A / mm
2
A / mm
2
100
194A / 50
185A / 50
177A / 50 151A / 50
145A / 50 139A / 50
280 / 70
M8
M10
120
232A / 70
222A / 70
213A / 70 181A / 50
174A / 50 166A / 50
336 / 95
M10
M10
150
290A / 95
278A / 95
266A / 95 227A / 70
217A / 70 208A / 70 421A/ 120
M10
M12
160
310A / 95
296A / 95
284A / 95 242A / 70
232A / 70 222A / 70 449A/ 120
M10
M12
200
387A / 120 370A / 120 355A / 120 303A /95
290A /95
277A / 95 560A/ 150
M12
M12
220
426A / 150 407A / 150 391A / 150 333A /120 319A /120 305A / 120 616A/ 185
M12
M12
5.4.1 Safety Earth
The safety earth cable must be connected to the earth BUS BAR and bonded to each cabinet in the system and
also the earthing and neutral bonding arrangements must be in accordance with the local laws.
ATTENTION!!!
Failure to follow adequate earthing procedures can result in electric shock hazard to personnel,
or the risk of fire.
5.4.2 Cable Connections
ATTENTION!!!
All the cable connections of the UPS must be done by the authorized service personnel. Once
the equipment has been finally positioned and secured, connect the power cables as described in the following
procedure: