12
At ALARMS MENU you can see LOG HISTORY, log events are recorded with event time and date.
PASSWORD
Menu is located for service purposes. This menu is developed for only adjustment.
Menu and submenu items
MAIN MENU
SUBMENU
MEANING
MEASURES MENU
LD%: 050 030 060
Output load
OPV: 220 221 219 V
Output voltage
FREQU: 50.0 Hz
Output frequency
IPV: 240 230 226 V
Input voltages
BYP: 225 221 219 V
Bypass source voltages
IPI: 031 040 020 A
Input currents
BATT: 432 V 06.7A
Battery voltage and charge current
TEMP: 24 C
Cabinet inside temperature
CHARGE LEVEL: 60%
Battery charge level
ENTER EXIT
Exit from submenu
ALARMS MENU
UPS STATUS
Valid alarm
000>DATE AND ALARM
Recorded log events
ENTER CLEAR LOG
Clearing log records
PARR.ERR.NR
Parallel control board error nr.
ENTER EXIT
Exit from submenu
INFORMATION MENU
SYNC :OK COMM :OK
Syncronization and comminication
POWER: 20000 VA
Output power of the UPS
VERSION : MC1XX
Version of UPS
FREQUENCY : PLL/XTAL
Frequency generation mode
ENTER EXIT
Exit from submenu
PASSWORD MENU
(password required )
System settings
ENTER EXIT
Exit from submenu
SETTINGS MENU
MODE:
Operation mode selection
UPS No :
UPS number selection
REMOTE :ENABLE
Remote access on/off
RESTART:ON/OFF
Mains restored setting
BYP.PROTECT ON
Bypass load protection
ENTER EXIT
Exit from submenu
COMMAND MENU
SOUND : ON/OFF
Sound alert on/off
ENTER B.TEST>432
Manuel battery test
ENTER <BYPASS>
Manuel bypass
ENTER:MODEM INIT
Modem settings
ENTER <BOOST>
Boost charge on/off
SIMULATION OFF
Simülation mode selection
ENTER EXIT
Exit from submenu
TIME MENU
TIME : 23 :15
time
DATE : 11-10-2001
date
SET HOURS: 11
Adjust hours
SET MINS : 38
Adjust minutes
SET DAY : 21
Adjust day
SET MONTH : 06
Adjust month
SET YEAR : 2001
Adjust year
ENTER <UPDATE>
Write new time and date
ENTER EXIT
Exit from submenu