14
2.7 INFORMATION Menu Items
This menu gives some information about UPS.
Submenu item
Function
1 SYNC :OK COMM :OK
If the UPS is operating syncron to mains SYNC:OK,if not syncron SYNC:--
If communication is active COMM:OK,if not active COMM:--
2 POWER: 20000 VA
The maximum power rating of the UPS
3 VERSION : MC1xx
Shows the UPS version
4 FREQUENCY : PLL
Frequency generation mode
PLL :phase locked loop is generating the frequency
XTAL : XTAL oscillator is generating the frequency
SLAVE : in parallel system master is generating the frequency
5 ENTER EXIT
Press ENTER
(
↵
)
to exit from this submenu
Goto first submenu item
2.8 SETTINGS Menu Items
From this menu user can set some important options.
Submenu item
Function
1 MODE: ONLINE
By using PLUS and MINUS keys you can move on 4 operation mode
options
ONLINE
: stand alone mode
PARALLEL
: 2 UPS in symmetric parallel operation
HOT STANDBY
: 1 UPS main the other UPS spare mode
REDUNDANT
: 2 UPS in redundant parallel mode.
→
press ENTER for 3 seconds and the selection is valid
2 UPS No : 001
By using PLUS and MINUS keys you can change number 0 to 3.
In parallel operation select different number for each UPS. If you select the
same number DUBL UPS NUMBER message tells the fault.
→
press ENTER for 3 seconds and the selection is valid
3 REMOTE :ENABLE
By using PLUS and MINUS keys you can change enable and disable
options.
enable
: remote battery test, shutdown and bypass function is enabled
disable
: these functions are disabled
→
press ENTER for 3 seconds and the selection is valid
4 RESTART:ON/OFF
By using PLUS and MINUS keys you can change on and off options.
ON
: during mains failure at the end of battery discharge UPS
shutdowns,after mains restored UPS startes again.
(battery trip out is on every time)
OFF
: during mains restore UPS don’t start again.
(battery trip out is off)
→
press ENTER for 3 seconds and the selection is valid
5 BYP.PROTECT ON
By using PLUS and MINUS keys you can change on and off options.
ON
: if the bypass source is out of tolerance UPS turn off load power.
OFF
: UPS turn off load power only for a shert peviod of time during
Transfer from inverter to by-pass supply.
6 ENTER EXIT
Press ENTER
(
↵
)
to exit from this submenu
Goto first submenu item
Summary of Contents for T-300P Series
Page 2: ......
Page 36: ...32 Figure 5 5 a UPS Battery Group Connection With Battery Fuse To UPS Cabinet Battery Fuse...
Page 44: ...40...
Page 45: ...41 AGKK1831 11 2010...