IMPORTANT NOTE:
Parallel system installation is much more complex from stand alone UPS installation, it needs
qualified service personnel.
You have to keep 80 cm distance between two UPS’s for service purposes.
Add 20% tolerance to cable sizes, fuses and circuit breakers in parallel connection.
In figure 3-2,the connections of 2 parallel UPS’s and load distribution panel are shown.
Figure 3-2
Parallel UPS Connection
U3 V3 W3 N3
BATTERY
INPUT
(
+
)
(
-
)
BATTERY
INPUT
(
+
)
(
-
)
U3 V3 W3 N3