background image

ECOCONDENS SILVER  PLUS                                                                                                   

ISU-646:2016/GR-H                                                                                        str.12 

 

Low-temperature circuits 
In the low-temperature area, it is recommended to treat the water by using heat transfer fluid HP-5 or Fernox AF10 biocide. 

 

Filtration technique 
Additionally, in order to ensure the quality of operation heating system, it is recommended to mount a modern filters, which works on 
the principle of the magnetic and cyclone effect, for example Fernox TF1 filter.  

 

Notice: 
- method and amount of use specific products for system cleaning and water treatment should be in accordance to the product 
manufacturer's instruction.   
- above steps should be made by the autorized installer or service technician.  

 

3.6.  Connection of the boiler to a domestic hot water system  

It is recommended to install cut-off valves on a domestic hot water system what will enable easier maintenance and service.  

It is recommended to install a water filter on the connection with the domestic water supply. This filter is not included 
in the standard boiler equipment. 

 

3.7. Condensate outlet 

Condensate formed during the combustion process must be drained according the following conditions: 

 

Installation of condensate drain must be made of corrosion-resistant material. 

 

Connection of draining the condensate cannot be blocked. 

 

To facilitate to drain the condensate through the flue gas all horizontal flue pipes must be installed with a fall of 3

o

 (52mm / m). 

 

3.8. Flue gas outlet 

Condensate formed during the combustion process must be drained according the following conditions: 
EcoCondens SILVER PLUS boilers could be installed as B-type appliances (where air needed for combustion is taken from the room 
where boiler is installed) or as C-type appliances  (where air needed for combustion is taken from outside). C-type appliances could be 
divided as follows: 

 

Depending on local regulations some types of installations might not be allowed. Always consult your local regulations before making 
flue-gas system project. 
Before turning on the boiler check if flue-gas system is made according to the project and air- and flue ducts lengths are shorter than 
maximum lengths showed in tables 3.8... Make sure flue-gas system is tight. 

 

After turning on the boiler check if it operates correctly. Also check combustion parameters by checking concentration of CO

2

 and/or 

O

2

 in flue-gas. 

Ways of connecting the boiler to the air-flue gas system 

  Fig. 3.8... 

 

To  ensure  proper  functioning  of  the  device  use  the  appropriate  wire  size  (diameter,  maximum  length,  resistance  on  the  knees),

 

depending  on  the  combustion  system  used.  The  dimensions  of  the  wires  should  be  adequately  compatible  as  given  in  table. 
Resistance of flue gas flow on each elbow depending on the bending angle and related reduction of the maximum wire length are given 
in section 3.8.6. 
Each system should be installed with the windproof outlet protecting against external factors. 

For  condensing  boilers  ECOCONDENS  SILVER  PLUS  there  are  provided  three  types  of  flue  gas-air  systems:  coaxial  system 

80/

125 and 

60/

100 and 2 separate 2 x 

80. It is possible to apply air-flue gas pipe made from polypropylene or stainless steel. 

The individual components of flue gas- air systems are given in table 7.1  

 

NOTICE: 
The boiler is factory adjusted for the coaxial exhaust system Ø60/100 of the maximum pipe length 3m + elbow. Settings O2 – 5%. To 
use the other systems and longer pipes it is required to adjust the boiler as specified in point 4.2. 
Coaxial reduction 

60/

100 x 

80/

125 shall be applied when using coaxial air-flue gas pipe 

80/

125. Inspection T-piece shall be 

applied when using air-flue gas pipe made from stainless steel. 
Condensing boilers SILVER PLUS meet the requirements to use in multi-storey air-flue gas systems LAS. 

3.8.1. The ways of mounting adapters (elbows connection) to the boiler type   

 

 

 

Coaxial system (air-flue gas pipe made from polypropylene) 

 

 
 
 
 

Summary of Contents for ECOCONDENS SILVER PLUS-20

Page 1: ...COMBI BOILERS SYSTEM BOILERS ECOCONDENS SIL VER PLUS 20 ECOCONDENS SIL VER PLUS 25 ECOCONDENS SIL VER PLUS 35 ECOCONDENS SIL VER PLUS 20 ECOCONDENS SIL VER PLUS 25 ECOCONDENS SIL VER PLUS 35 1450...

Page 2: ...system Filters are not included in a basic boiler equipment An example of connecting a boiler to these systems is presented on fig 3 5 1 All defects caused by lack of filters on central heating or gas...

Page 3: ...ing on the boiler s type Shut off the filling valve after reaching the pressure of 1 0 1 5 bar Note in some models of boilers after end of the start procedure the support the venting of boiler functio...

Page 4: ...ction of a room temperature regulator 15 3 10 CONNECTING THE OUTSIDE TEMPERATURE SENSOR 15 4 BOILER ADJUSTMENT AND PRELIMINARY SETTING 15 4 1 INTRODUCTORY REMARKS 15 4 2 ADJUSTING THE BOILER TO COMBUS...

Page 5: ...tallation B23 Further information regarding the type according section 3 8 and PN EN 15502 2 1 2013 04 2 BOILER DESCRIPTION 2 1 Technical specification 2 1 1 Technical features 2 2 Design and technica...

Page 6: ...on of elements in system boiler ECOCONDENS SILVER PLUS Only Fig 2 2 1 3 1 Swich of boiler function selection 2 Temperature selector c h or d h w 3 Heating water domestic water and static pressure temp...

Page 7: ...e boiler at nominal load and average boiler water temperature of 70 C 97 6 98 0 98 0 Water heating energy efficiency class A A A Load profile L XL XL Water pressure MPa bar 0 01 0 1 0 6 6 Min water fl...

Page 8: ...power supply of the three way valve item 12 towards the central heating installation pump supply item 7 fan supply item 5 the sequence of ignition then the driver starts the fan speed regulation so as...

Page 9: ...C Domestic water temperature on the inlet t 5 C Fig 2 4 3 2 Diagram of domestic water temperature at the boiler outlet at thermal power of 30kW depending on the water flow rate 9 50 15 0 10 5 25 30 20...

Page 10: ...es the pump according to For conventional PWM pump operation parameter P 15 0 PWM Pump activation by parameter P12 works with a modulated speed in C H system activating by signal from RT room temperat...

Page 11: ...should be protected against freezing free from dust and aggressive gases It is forbidden to install the device in a laundry rooms drying rooms and in varnish cleaners solvents and sprays storages Boi...

Page 12: ...the wall Hang the boiler on hooks fastened durably in the wall using a beam placed in upper part of the boiler The boiler shall be so located as to permit the eventual repair without any need to disma...

Page 13: ...e device its parameters and components life After boiler installation Fill the heating system with water by filling valve item 22 Fig 2 2 1 1 for combi boiler For system boiler install filling valve f...

Page 14: ...ulations some types of installations might not be allowed Always consult your local regulations before making flue gas system project Before turning on the boiler check if flue gas system is made acco...

Page 15: ...ER PLUS 35 Maximum length of chimney flue Lmax 20m L max 60 100 80 125 or coaxial reduction O60 100 x O80 125 Coaxial elbow 90 O60 100 Coaxial elbow 90 O80 125 3 8 3 Vertical outlet of air flue gas sy...

Page 16: ...er index T9000 00 54 00 sealing the connection with a gasket In place of flue gas outlet after the dismantling of the coaxial adapter 60 100 and reducing ring 60 80 the adapter should be screwed index...

Page 17: ...10 Connecting the outside temperature sensor To connect the outside temperature sensor use the 2 wire cable 2x0 5mm 2 50m max and connect it to terminals 3 and 4 AFS located under the right flap Fig 3...

Page 18: ...gas flow rate on the gas meter for compliance with Table 4 3 2 1 If you need to change the gas flow turn the screw pos 6 Fig 4 2 1 Turn the screw to the left to increase the flow turn the screw to th...

Page 19: ...99 P03 77 P02 99 P03 87 P02 99 The content of CO2 in the flue gas The content of CO2 in the flue gas 11 0 0 5 11 0 0 5 Gas flow rate l min Gas flow rate l min 3P G31 37 1 8 0 5 2 6 0 5 2 8 0 5 13 4 1...

Page 20: ...heating Service function Anti legionella function active only for boilers with tanks SUMMER Press button for about 1 second changing the operating mode to mode SUMMER D H W heating Anti legionella fu...

Page 21: ...to support venting of the heating system It consists of successive six cycles switching on the pump for 15 sec and switching off the pump for 15 sec alternately in CH and DHW circuit Lock of heating...

Page 22: ...ding on boiler type Parameter is visible when the CM clamp is removed P07 Type of CH circuit 1 closed 1 Boiler adapted for closed central heating system P08 Type of heating 0 1 0 standard heating 1 fl...

Page 23: ...ND BY section 5 3 In such conditions the controller of the boiler has a protective function described in point 5 3 Performed functions If You decide to discontinue use of the boiler for a long time yo...

Page 24: ...thermal fuse was burned off and the boiler was switched off with blockade Call Authorized Service Company Damage in the circuit of NTC sensor of heating water temperature The burner is turned off Call...

Page 25: ...ld be replaced Note Dirty burner and the interior of the combustion chamber mean that the boiler regulation must be done In order to get into the combustion chamber burner and electrode close the gas...

Page 26: ...panel Measure the sensor resistance Temperature C NTC DHW and NTC CH sensor resistance NTC tank sensor and temperature sensor resistance Sensor 3977 10 55218 0 75 0 32624 0 75 10 19897 0 75 20 12 480...

Page 27: ...x 230V AC 7 Pump Yonos Para PWM Power 45W 230V AC 8 Gas unit SIT SIGMA 848 Valve coil resistance 3 4 EV1 0 9 k 1 3 EV2 6 4 k 230V AC 18 NTC sensor of CH water temperature 10K 25 C 3977 SELV 19 Heating...

Page 28: ...lator Fig 6 2 1 Schematic diagram of the electrical connections 6 3 The maintenance operations to be performed by the user User should clean the water filter periodically preferably before the heating...

Page 29: ...ion 60 100 x 80 125 T9000016700 1 Elements of the system according to the installation design 1 set Flue gas air system coaxial 60 100 Fig 3 8 2 1 4 Coaxial elbow 60 100 90 with revision T9000015 300...

Page 30: ...nstallation design 1 set Flue gas air system coaxial 60 100 Fig 3 8 3 1 6 Coaxial inspection T piece T9000007200 1 ECOCONDENS SILVER PLUS Not included in boiler equipment Elements of the system accord...

Page 31: ......

Reviews: