background image

ECOCONDENS SILVER  PLUS                                                                                                   

ISU-646:2016/GR-H                                                                                        str.11 

 

  Install a water filter on a water return from central heating system (in front of the connection with the pump). The filter is 

not included in standard boiler equipment.  

  The central heating system should be thoroughly rinsed out before the boiler is connected.  

  In  the  central  heating  system  it  is  permitted  to  use  as  a  heat  carrier  any  antifreeze  fluids  which  can  be  used  in  central  heating 

systems. 

  The  cut-off  valves  needs  to  be  installed  between  the  boiler  and  central  heating  system  so  that  the  boiler  could  be  dismounted 

without draining the system. 

  Do not install any thermostatic valves on radiators in the room where the thermostat is installed. The temperature controller takes 

the control over the function of temperature and it cooperates with the boiler. 

  On at least one of radiators of the central heating system there shouldn`t be installed a thermostatic valve. 

  It is recommended to lead out a water from a safety valve 0,3 MPa (3 bar) (item 25) to a floor drain by a tube or hose otherwise 

during the safety valve activation there is a risk of flooding a room what is excluded of producer’s liability.  

Selection of expansion vessel 

Boilers  ECOCONDENS  SILVER  PLUS  are  adjusted  to  be  connected  to  a  central  heating  system  with  the maximum  capacity  of  105 
liters.  The  assembly  to  installation  with  larger  capacity  is  acceptable  only  after  applying  an  additional  expansion  vessel.  A  proper 
expansion vessel should be selected by the designer of central heating system.  
Installation of expansion vessel should be made by an installation contractor in accordance with applicable regulations. 

 

NOTICE! : Before installing the boiler thoroughly flush the central heating system to free it from any solid impurities.    
It  is  recommended  that  after  first  start  up  of  the  boiler  and  heating  up  of  the  installation  drain  the  water  from  the  system  to  remove 
residues of pastes metallurgical and precautionary measures of heaters. These activities would benefit for the operation of the device, 
its parameters and components life. 

After boiler installation: 

 

Fill the heating system with water by filling valve 

 item 22 Fig 2.2.1.1. for combi boiler. For system boiler install filling valve from 

the installation. Pressure in cold installation should amount 1,0 to 1,5 bar (indicated by manometer). 

 

Vent the installation of central heating and boiler; 

 

Check the tightness of boiler connections in central heating system. 

From the water system

Floor drain

From the water system

Floor drain

F

lu

e

 g

a

s

 o

u

tl

e

t

G

a

s

 f

ilt

e

r

W

a

te

fi

lt

e

r

Gas

Exhaust ventilation

Exhaust ventilation

F

lu

e

 g

a

s

 o

u

tl

e

t

G

a

s

 f

ilt

e

r

Gas

W

a

te

fi

lt

e

r

 

Fig. 3.5.1 Boilers installation requirements 

 

3.5.2

 

System cleaning and water treatment for the C.H. filling.

 

Every  component  of  C.H.  system  is  threatened  by  limestone  deposits,  corrosion  and  other  dangerous  processes.  Boiler  is  the  most 
expensive  part  of  C.H.  system  and  it  is  necessary  to  protect  its  components  like  heat  exchanger  and  other  parts  against  harmful 
processes. Correct C.H. circuit preparation for using relies on making two operations: cleaning the CH system and treating the water 
that fills the system. 

 

System cleaning 
In  new  installation  it  is  possible  to  find  some  remains  of  industrial  process  jak  soldering  and  welding  remains,  flux,  oil  and  grease 
residue among others. Older installations usually have products of corrosion in them. It necessary to clean up the systems with a water 
to  remove  the  remains  before  boiler  is  mounted.  Afterwards,  system  should  be  cleaned  with  appropriate  chemicals.  For  example 
Cleaner F3 from Fernox in new installations. For old and contaminated systems it is best to use Cleaner F5). Afer that it is necessary to 
rinse the installation with water.  

 

Water treatment to fill the system 
For  filling  the  system,  it  is  recommended  to  use  water  with  parameters:  pH  6,5-  8,5,  hardness  <  10  °n  (~  18°F).  Do  not  use 
demineralised  or  destilled  water.  To  ensure  protection  against  rocks  despositing,  corrosion,  it  is  recommended  to  use  a  special 
inhibitor, for example Fernox Protector F1. Heat transfer fluid HP-5 or antifreeze liquid can also be used, for example  Fernox Alphi 11. 
If the water hardness is very high, the HP-5 effectively reduces the risk of heat exchanger calcification. 

 

Summary of Contents for ECOCONDENS SILVER PLUS-20

Page 1: ...COMBI BOILERS SYSTEM BOILERS ECOCONDENS SIL VER PLUS 20 ECOCONDENS SIL VER PLUS 25 ECOCONDENS SIL VER PLUS 35 ECOCONDENS SIL VER PLUS 20 ECOCONDENS SIL VER PLUS 25 ECOCONDENS SIL VER PLUS 35 1450...

Page 2: ...system Filters are not included in a basic boiler equipment An example of connecting a boiler to these systems is presented on fig 3 5 1 All defects caused by lack of filters on central heating or gas...

Page 3: ...ing on the boiler s type Shut off the filling valve after reaching the pressure of 1 0 1 5 bar Note in some models of boilers after end of the start procedure the support the venting of boiler functio...

Page 4: ...ction of a room temperature regulator 15 3 10 CONNECTING THE OUTSIDE TEMPERATURE SENSOR 15 4 BOILER ADJUSTMENT AND PRELIMINARY SETTING 15 4 1 INTRODUCTORY REMARKS 15 4 2 ADJUSTING THE BOILER TO COMBUS...

Page 5: ...tallation B23 Further information regarding the type according section 3 8 and PN EN 15502 2 1 2013 04 2 BOILER DESCRIPTION 2 1 Technical specification 2 1 1 Technical features 2 2 Design and technica...

Page 6: ...on of elements in system boiler ECOCONDENS SILVER PLUS Only Fig 2 2 1 3 1 Swich of boiler function selection 2 Temperature selector c h or d h w 3 Heating water domestic water and static pressure temp...

Page 7: ...e boiler at nominal load and average boiler water temperature of 70 C 97 6 98 0 98 0 Water heating energy efficiency class A A A Load profile L XL XL Water pressure MPa bar 0 01 0 1 0 6 6 Min water fl...

Page 8: ...power supply of the three way valve item 12 towards the central heating installation pump supply item 7 fan supply item 5 the sequence of ignition then the driver starts the fan speed regulation so as...

Page 9: ...C Domestic water temperature on the inlet t 5 C Fig 2 4 3 2 Diagram of domestic water temperature at the boiler outlet at thermal power of 30kW depending on the water flow rate 9 50 15 0 10 5 25 30 20...

Page 10: ...es the pump according to For conventional PWM pump operation parameter P 15 0 PWM Pump activation by parameter P12 works with a modulated speed in C H system activating by signal from RT room temperat...

Page 11: ...should be protected against freezing free from dust and aggressive gases It is forbidden to install the device in a laundry rooms drying rooms and in varnish cleaners solvents and sprays storages Boi...

Page 12: ...the wall Hang the boiler on hooks fastened durably in the wall using a beam placed in upper part of the boiler The boiler shall be so located as to permit the eventual repair without any need to disma...

Page 13: ...e device its parameters and components life After boiler installation Fill the heating system with water by filling valve item 22 Fig 2 2 1 1 for combi boiler For system boiler install filling valve f...

Page 14: ...ulations some types of installations might not be allowed Always consult your local regulations before making flue gas system project Before turning on the boiler check if flue gas system is made acco...

Page 15: ...ER PLUS 35 Maximum length of chimney flue Lmax 20m L max 60 100 80 125 or coaxial reduction O60 100 x O80 125 Coaxial elbow 90 O60 100 Coaxial elbow 90 O80 125 3 8 3 Vertical outlet of air flue gas sy...

Page 16: ...er index T9000 00 54 00 sealing the connection with a gasket In place of flue gas outlet after the dismantling of the coaxial adapter 60 100 and reducing ring 60 80 the adapter should be screwed index...

Page 17: ...10 Connecting the outside temperature sensor To connect the outside temperature sensor use the 2 wire cable 2x0 5mm 2 50m max and connect it to terminals 3 and 4 AFS located under the right flap Fig 3...

Page 18: ...gas flow rate on the gas meter for compliance with Table 4 3 2 1 If you need to change the gas flow turn the screw pos 6 Fig 4 2 1 Turn the screw to the left to increase the flow turn the screw to th...

Page 19: ...99 P03 77 P02 99 P03 87 P02 99 The content of CO2 in the flue gas The content of CO2 in the flue gas 11 0 0 5 11 0 0 5 Gas flow rate l min Gas flow rate l min 3P G31 37 1 8 0 5 2 6 0 5 2 8 0 5 13 4 1...

Page 20: ...heating Service function Anti legionella function active only for boilers with tanks SUMMER Press button for about 1 second changing the operating mode to mode SUMMER D H W heating Anti legionella fu...

Page 21: ...to support venting of the heating system It consists of successive six cycles switching on the pump for 15 sec and switching off the pump for 15 sec alternately in CH and DHW circuit Lock of heating...

Page 22: ...ding on boiler type Parameter is visible when the CM clamp is removed P07 Type of CH circuit 1 closed 1 Boiler adapted for closed central heating system P08 Type of heating 0 1 0 standard heating 1 fl...

Page 23: ...ND BY section 5 3 In such conditions the controller of the boiler has a protective function described in point 5 3 Performed functions If You decide to discontinue use of the boiler for a long time yo...

Page 24: ...thermal fuse was burned off and the boiler was switched off with blockade Call Authorized Service Company Damage in the circuit of NTC sensor of heating water temperature The burner is turned off Call...

Page 25: ...ld be replaced Note Dirty burner and the interior of the combustion chamber mean that the boiler regulation must be done In order to get into the combustion chamber burner and electrode close the gas...

Page 26: ...panel Measure the sensor resistance Temperature C NTC DHW and NTC CH sensor resistance NTC tank sensor and temperature sensor resistance Sensor 3977 10 55218 0 75 0 32624 0 75 10 19897 0 75 20 12 480...

Page 27: ...x 230V AC 7 Pump Yonos Para PWM Power 45W 230V AC 8 Gas unit SIT SIGMA 848 Valve coil resistance 3 4 EV1 0 9 k 1 3 EV2 6 4 k 230V AC 18 NTC sensor of CH water temperature 10K 25 C 3977 SELV 19 Heating...

Page 28: ...lator Fig 6 2 1 Schematic diagram of the electrical connections 6 3 The maintenance operations to be performed by the user User should clean the water filter periodically preferably before the heating...

Page 29: ...ion 60 100 x 80 125 T9000016700 1 Elements of the system according to the installation design 1 set Flue gas air system coaxial 60 100 Fig 3 8 2 1 4 Coaxial elbow 60 100 90 with revision T9000015 300...

Page 30: ...nstallation design 1 set Flue gas air system coaxial 60 100 Fig 3 8 3 1 6 Coaxial inspection T piece T9000007200 1 ECOCONDENS SILVER PLUS Not included in boiler equipment Elements of the system accord...

Page 31: ......

Reviews: