TCW242-S_R1.0 – July 2021
Page 49
13 – “Major”
14 – “Critical”
Alarms - values/descriptions Alarms 1 to 24 values/descriptions
Following alarm values are available:
0 – “Undefined”
1 – “Normal”
2 – “Indeterminate”
3 – “Warning”
4 – “Minor”
5 – “Major”
6 – “Critical”
An example of the log file /fragment channels - values/units/:
ID;Time;Type;Ch1/°C;Ch2/%RH;Ch3;Ch4;Ch5;Ch6;Ch7;Ch8;Ch9;Ch10;Ch11;Ch12;Ch13;Ch14;Ch15;Ch16;Ch17;Ch18;Ch19;Ch20;Ch21;Ch22;Ch23;Ch24....
25114;19.07.2021,16:49:49; Time;25.319;54.512;118.833;229.877;0.000;6587.396;;;;;;;;;;;;;;;;;;;….
An example of the log file /fragment relays - conditions/:
ID;Time;Type;…R1,R2,R3,R4....
25114;19.07.2021,16:49:49; Time;1,1,0,0;;;;;;;;;;;;;;;;;;;….
An example of the log file /fragment channels - states/units/:
ID;Time;Type;….ChSt1/°C;ChSt2/%RH;ChSt3;ChSt4;ChSt5;ChSt6;ChSt7;ChSt8;ChSt9;ChSt10;ChSt11;ChSt12;ChSt13;ChSt14;ChSt15;ChSt16;ChSt17;ChSt18;
ChSt19;ChSt20;ChSt21;ChSt22;ChSt23;ChSt24....
25114;19.07.2021,16:49:49;Time;….3;5;0;2;2;2;;;;;;;;;;;;;;;;;;;….
An example of the log file /fragment alarms - values/descriptions/:
ID;Time;Type;…Al1/AL1-T;Al2/AL2-H;Al3;Al4;Al5;Al6;Al7;Al8;Al9;Al10;Al11;Al12;Al13;Al14;Al15;Al16;Al17;Al18;Al19;Al20;Al21;Al22;Al23;Al24....
25114;19.07.2021,16:49:49;Time;….3;5;0;0;0;0;;;;;;;;;;;;;;;;;;
11.
Factory default settings
TCW242-S can be restored to its original factory default settings in 3 different ways.
11.1.
Factory default from the WEB interface
If the button “Factory default” from Administration->Backup/Restore is pressed, all parameters
return to factory default except Network settings.
11.2.
Factory default with the reset button
If the reset button is pressed for more than 5 seconds, while the device is working, all Network
settings go to factory default.
11.3.
General factory default with the reset button
For factory default reset of all parameters following steps should be executed:
Press and hold the RESET button, then turn on the power supply;
Yellow LED shines and red LED blinks about 5 times on а second;
After about 5 seconds red LED will turn off, the button can be released;
Yellow LED flashes on 1 second and red LED shines – the device is in working mode, with
factory default settings.
Summary of Contents for TCW242-S
Page 1: ......
Page 52: ...TCW242 S_R1 0 July 2021 Page 52 Appendix A Fig 1 Fig 2...