TCW242-S_R1.0 – July 2021
Page 10
If the network settings are correct, the login pop-up window will appear:
Authorization data must be entered (by default username=admin, password=admin).
It is recommended to change the username and password to prevent unauthorized access to the
controller.
All TCW controllers connected to LAN can be easily found by a free tool “TCW discoverer”. It is
available for Win and Mac operating systems and can be downloaded from
www.teracomsystems.com.
7.
Concept of setup
The main setup channel of the device is the web interface. It is recommended to use it, even more of
the settings are available through SNMP and HTTP API commands.
The device setup begins with network settings.
Then the so-called primary parameters (MODBUS RTU sensors/registers, analog inputs, and digital
inputs) are set up.
The channels are formed from already set up primary parameters. Every channel can combine up to
two primary parameters and constants with math operations. It is possible that a channel is formed by
only one primary parameter.
Once all channels have been tuned, the alarm can be set up. It is important to remember that alarms
work with channels, not with primary parameters. Each alarm can have up to two conditions. Different
channels may be involved in the conditions. Alarms are independent of the channels but can also be
assigned to a channel.
In other words, the right setup should follow the following order:
Once everything above is set correctly, the wanted services (data logger, SNMP, HTTP API, etc.) can be
turned on.
8.
Web interface
The web interface allows configuration and monitoring. All pages are UTF-8 encoded.
The controller supports a few active sessions. For the WEB interface, the device supports HTTP only
(HTTPS is not supported).
8.1.
Monitoring
This section displays the status of all channels, relays, and alarms – textually and graphically.
The pages “Data” and “Alarms” are refreshed automatically on at interval of 0 to 253 seconds. Zero
means no automatic refresh. This parameter is set in section “Setup-System- Refresh of channels
and alarms pages”. By default, the refresh interval is 1 second.