For  locally  activated  relays  a  text  description  of  the  controlling  parameter  is  displayed  rather 
than  buttons.  Parameters  for  local  relay  activation  can  be  set  in  “Setup-Input/Output-Relay 
Outputs”. 

8.2.4.

 

Channels 

This section allows you to add, delete or edit channels. All they can be monitored on monitoring 
pages and their values can be recorded periodically by the data logger.  

Up to 24 channels can be set up. 

 

There are two types of channels – discrete (it forms by one digital input in OPEN/CLOSE mode) 
and general (it forms by up to 2 primary parameters and constants)  

It is important to know that for general channels, the sequence of operations is  OP1, then OP2, 
and finally OP3. 

It is possible to use a digital input in OPEN/CLOSE mode to form a general channel. In this case, 
its values for operations are 0 (for CLOSE) and 1 (for OPEN). 

8.2.5.

 

 

Alarms 

This section allows you to add, delete or edit alarms. Up to 24 alarms can be set up. 

There are four types of alarms – Warning, Minor, Major and Critical.  

Only channels can be used to form the alarms. 

The alarms are independent but can be assigned to a channel. There isn’t a restriction to which 
channel to assign the alarm. 

For every alarm up to 2 conditions can be used. Both conditions can be logically joined using the 
logical operators AND and OR. 

It is not mandatory to use the same channel in both conditions. In this case, conditions for two 
different channels can be combined in one alarm. 

 

 

Summary of Contents for TCW242-S

Page 1: ......

Page 2: ...teresis The alarm can be assigned to a specific channel In this case in an alarm state the assigned channel is colored on the monitoring page and graphs The device supports SNMP HTTP API and MODBUS TC...

Page 3: ...rent pin 7 of RJ 45 0 2 A Digital inputs Isolation Non isolated Mode OPEN CLOSED Dry contact or COUNTER Maximum input voltage 5 5VDC Sampling rate 1mS Digital filtering time interval 5 to 60000mS Anal...

Page 4: ...ecting to an IP network connecting inputs and outputs providing power and configuring via a web browser 6 1 Mounting TCW242 S should be mounted in a clean and dry location on a non flammable surface V...

Page 5: ...n 3 Pin8 COM Relay2 Pin5 GND Pin9 NO Relay2 Pin6 Digital In 4 Pin10 NC Relay1 Connector 8 Pin1 Analog In 1 Pin11 COM Relay1 Pin2 GND Pin12 NO Relay1 Pin3 Analog In 2 Connector 5 Pin1 Line A D0 Pin4 An...

Page 6: ...ntact pulse output interface The maximum cable length should be up to 30 meters 6 2 3 Analog inputs connection All inputs are non isolated from the power supply Analog inputs of TCW242 S can be used f...

Page 7: ...n the document MODBUS over Serial Line Specification and Implementation Guide available on www modbus org It is mandatory to use 120ohms line terminators at both ends of the bus TCW242 S incorporates...

Page 8: ...o the Ethernet port on a computer The device support Auto MDIX and it is not necessary to use a crossover cable standard straight through can be also used TCW242 S can be used in a wireless network by...

Page 9: ...a temporary IP address to the computer For computers with Windows OS assigning of IP address is made in Local area connection properties This address should be on the same network for example 192 168...

Page 10: ...th operations It is possible that a channel is formed by only one primary parameter Once all channels have been tuned the alarm can be set up It is important to remember that alarms work with channels...

Page 11: ...s The information is updated on the refresh interval 8 1 3 Graphs All channels together with their alarm statuses can be monitored graphically in tabs Graph 1 to Graph 6 Every graph supports up to 4 c...

Page 12: ...verer It is recommended to use a public DNS server 8 8 8 8 8 8 4 4 etc rather than the default gateway 8 2 2 Modbus sensors 8 2 2 1 Modbus RTU communication setup Modbus RTU communication setup This s...

Page 13: ...ter set Multiplier 1 and Offset 0 During operation all sensors are polled consecutively The controller expects an answer in response time out If the sensor does not respond for that time the controlle...

Page 14: ...lays analog and digital inputs 8 2 3 1 Analog inputs TCW242 S has 4 analog inputs All they are isolated from the power supply but use the same ground Every analog input can work in voltage 0 10V or cu...

Page 15: ...n COUNTER mode counting can be made on rising falling or both edges For the counter mode there is a possibility for setting up the counter initial value There are two delays Open to Close and Close to...

Page 16: ...general channels the sequence of operations is OP1 then OP2 and finally OP3 It is possible to use a digital input in OPEN CLOSE mode to form a general channel In this case its values for operations a...

Page 17: ...when the value goes higher than Limit Hysteresis Sign is or lower than Limit Hysteresis Sign is The hysteresis is used to prevent excessive triggering when the value vacillates around the trigger poi...

Page 18: ...HTTP port for WEB access by default is 80 but it can be changed This is useful for some routers which don t support different outside inside ports for port forwarding HTTP API access authentication by...

Page 19: ...d SNMPv3 The default parameters are SNMP disabled Port 161 SNMPv3 disabled read community public write community private Security User Name teracom Security Level noAuthNoPriv Authentication Protocol...

Page 20: ...ve algorithm None authentication User based Privacy Mechanism is based on the following Data Encryption Standard DES Advanced Encryption Standard AES None encryption For alarm notification an SNMP tra...

Page 21: ...s very useful when monitoring electricity water gas meters etc The log interval can be chosen from a drop down menu between 1 and 60 minutes The field Sync to the minute determines which minute of eve...

Page 22: ...gger section 8 3 4 HTTP Post TCW242 S can periodically upload an XML JSON file to a dedicated server using HTTP or HTTPS Post The HTTPS is over TLS 1 0 TLS 1 1 and TLS 1 2 with RSA as a key exchange a...

Page 23: ...P API section 8 3 5 Schedule TCW242 S supports four schedules In every schedule up to four different tasks can be set The schedules are useful for creating tasks that vary with calendar dates It is po...

Page 24: ...and ends at 17 00 weekly task for a time period which includes the midnight With the above setting there will be an event for 2 hours between Monday 23 00 00 and Tuesday 01 00 00 8 3 6 Dynamic DNS TCW...

Page 25: ...ettings to a batch of controllers 8 4 3 FW update The TCW242 S can be updated via a WEB interface To update the device follow the steps below Go to www teracomsystems com and download the latest firmw...

Page 26: ...2 2 1 1 1 2 0 mbSenDescription read write Sensor description DisplayString 8 2 2 1 1 1 3 0 mbSenMult read write Sensor multiplier x1000 in Integer format Integer32 8 2 2 1 1 1 4 0 mbSenOffset read wri...

Page 27: ...24 24 anyAlarm 25 schedule1 26 schedule2 27 schedule3 28 schedule1 29 8 2 2 4 1 1 5 0 relOutAction read write Relay action on alarm condition INTEGER on 0 pulse 2 OID Name Access Description Syntax 8...

Page 28: ...1 3 6 1 4 1 38783 in the table below OID Name Access Description Syntax 8 3 2 1 1 2 0 relayState read write Relay state INTEGER off 0 on 1 8 3 2 1 1 3 0 relayPulse read write Relay pulse INTEGER off...

Page 29: ...22 v23 23 v24 24 8 3 3 1 1 16 0 alActionDelay read write Alarm action delay Integer32 8 3 3 1 1 17 0 alActionOnReturn read write Alarm action on return INTEGER no 0 yes 1 8 3 3 1 1 18 0 alAction1 rea...

Page 30: ...POST datePrefix date YmdHis strtotime now pathname FOLDER SEPARATOR datePrefix _ FILENAME postdata file_get_contents php input handle fopen pathname w content var_export postdata true fwrite handle su...

Page 31: ...Commands All commands used with HTTP HTTPS Post can be used also with HTTP Get The right format is http device ip address status xml yyy xxx Where yyy is the command xxx is the parameter Example http...

Page 32: ...17 characters ron n Turn relay m ON m is 1 2 3 or 4 n is 1 2 4 or 8 ron 1 will turn ON relay 1 ron 2 will turn ON relay 2 ron 4 will turn ON relay 3 ron 8 will turn ON relay 4 ron 1 ron 2 ron 4 ron 8...

Page 33: ...e 51 323 value unit RH unit alarmbin 1 alarmbin alarm Normal alarm selch 4 selch CH2 CH3 type 2 type description Digital Input 1 description value OPEN value unit alarmbin 1 alarmbin alarm Normal alar...

Page 34: ...scription V11 description value value unit alarmbin 0 alarmbin alarm selch 0 selch CH11 CH12 type 0 type description V12 description value value unit alarmbin 0 alarmbin alarm selch 0 selch CH12 CH13...

Page 35: ...alarmbin alarm selch 0 selch CH19 CH20 type 0 type description V20 description value value unit alarmbin 0 alarmbin alarm selch 0 selch CH20 CH21 type 0 type description V21 description value value un...

Page 36: ...mbin alarm assign 2 assign AL5 AL6 description AL06 description alarmbin 0 alarmbin alarm assign 0 assign AL6 AL7 description AL07 description alarmbin 0 alarmbin alarm assign 0 assign AL7 AL8 descrip...

Page 37: ...n alarmbin 0 alarmbin alarm assign 0 assign AL18 AL19 description AL19 description alarmbin 0 alarmbin alarm assign 0 assign AL19 AL20 description AL20 description alarmbin 0 alarmbin alarm assign 0 a...

Page 38: ...AL1 AL24 alarms R1 R4 relays alarmbin number values from 0 to 6 alarm Undefined Normal Indeterminate Warning Minor Major Critical assign 0 assign alarm not assigned to any channel selch 0 selch channe...

Page 39: ...V alarmbin 1 alarm Normal selch 27 CH6 type 0 description V06 Current value 0 000 unit A alarmbin 1 alarm Normal selch 28 CH7 type 1 description V07 Energy value 6587 396 unit kWh alarmbin 0 alarm sel...

Page 40: ...14 type 0 description V14 value unit alarmbin 0 alarm selch 0 CH15 type 0 description V15 value unit alarmbin 0 alarm selch 0 CH16 type 0 description V16 value unit alarmbin 0 alarm selch 0 CH17 type...

Page 41: ...0 alarm selch 0 CH23 type 0 description V23 value unit alarmbin 0 alarm selch 0 CH24 type 0 description V24 value unit alarmbin 0 alarm selch 0 AL AL1 description AL01 T alarmbin 4 alarm Minor assign...

Page 42: ...cription AL10 alarmbin 0 alarm assign 0 AL11 description AL11 alarmbin 0 alarm assign 0 AL12 description AL12 alarmbin 0 alarm assign 0 AL13 description AL13 alarmbin 0 alarm assign 0 AL14 description...

Page 43: ...armbin 0 alarm assign 0 AL23 description AL23 alarmbin 0 alarm assign 0 AL24 description AL24 alarmbin 0 alarm assign 0 R R1 description Relay 1 value ON valuebin 1 R2 description Relay 2 value OFF va...

Page 44: ...er of coils requested the last data field 01 contains the status of only 1 coil The 7 most significant bits in this data field are filled in with zeroes The activated relay is 1 9 3 1 2 Force Single C...

Page 45: ...0 16 bytes value All holding registers with strings are sent in big endian The answer is padded with 0 In the example above the string Temperature is sent 9 3 1 4 Exception codes All exceptions are si...

Page 46: ...annel 22 03 440 32 bit Float Read Channel 23 03 442 32 bit Float Read Channel 24 03 444 32 bit Float Channels 1 24 type Counter Read Channel 1 03 500 32 bit unsign int Read Channel 2 03 502 32 bit uns...

Page 47: ...el 20 Dimension 03 1152 16 bytes UTF 8 Read Channel 21 Dimension 03 1160 16 bytes UTF 8 Read Channel 22 Dimension 03 1168 16 bytes UTF 8 Read Channel 23 Dimension 03 1176 16 bytes UTF 8 Read Channel 2...

Page 48: ...intervals 1 2 3 4 6 8 12 and 24 hours The file is in CSV format A semicolon is used as a delimiter The first row of the log file is always the header All rows including the header start with a record...

Page 49: ...agment alarms values descriptions ID Time Type Al1 AL1 T Al2 AL2 H Al3 Al4 Al5 Al6 Al7 Al8 Al9 Al10 Al11 Al12 Al13 Al14 Al15 Al16 Al17 Al18 Al19 Al20 Al21 Al22 Al23 Al24 25114 19 07 2021 16 49 49 Time...

Page 50: ...requirements and shall be intended for use in the same ambient conditions 13 Safety This device must not be used for medical life saving purposes or for any purpose where its failure could cause seri...

Page 51: ...ird party sensor proper parameters value should be displayed At the same time flashing STS led should indicate the proper operation If the equipment is used in a manner not specified by the manufactur...

Page 52: ...TCW242 S_R1 0 July 2021 Page 52 Appendix A Fig 1 Fig 2...

Reviews: