TCW242-S_R1.0 – July 2021
Page 26
9.
Protocols and API
9.1.
SNMP
Simple Network Management Protocol (SNMP) is a standard internet protocol for managing devices
on IP networks. In typical usage of SNMP, one or more administrative computers, called managers,
monitor and control devices on LAN. Each controlled device, at all times, executes a software
component called an agent which reports information via SNMP to the manager.
The
TCW242-S can be configured and monitored through SNMP.
This could be done using every SNMP v.2 or v.3 compatible program. Parameters that can be
changed, are grouped according to their functions in the tables below. To obtain a valid OID
number, replace the symbol “
!
” with ”1.3.6.1.4.1.38783”.
To save the changes
configurationSaved
(OID !.8.6.3.0) should be set to "1".
product
OID
Name
Access
Description
Syntax
!.
8.1.1.0
name
read-only
Device name
DisplayString
!.
8.1.2.0
version
read-only
Firmware version
DisplayString
!.
8.1.3.0
date
read-only
Release date
DisplayString
setup -> network
replace “
!
” with ”1.3.6.1.4.1.38783” in the table below
OID
Name
Access
Description
Syntax
!.
8.2.1.1.0
deviceID
read-only
Device ID (default MAC address)
MacAddress
!.
8.2.1.2.0
hostName
read-only
Hostname
DisplayString
(SIZE (0..38))
!.
8.2.1.3.0
deviceIP
read-only
Device IP address
IpAddress
setup -> parameters -> mbSensors -> mbSensorsTable -> mbSensorsEntry -> msSensIndex 1 to 24
replace “
?
“ with a number from 1 to 24 and “
!
” with ”1.3.6.1.4.1.38783” in the table below
OID
Name
Access
Description
Syntax
!.
8.2.2.1.1.1.2.
?
.0
mbSenDescription.
?
read-write
Sensor description
DisplayString
!.
8.2.2.1.1.1.3.
?
.0
mbSenMult.
?
read-write
Sensor multiplier x1000 in Integer format
Integer32
!.
8.2.2.1.1.1.4.
?
.0
mbSenOffset.
?
read-write
Sensor offset x1000 in Integer format
Integer32
!.
8.2.2.1.1.1.5.
?
.0
mbSenVal.
?
read-only
Sensor value x1000 in Integer format
Integer32
!.
8.2.2.1.1.1.6.
?
.0
mbSenCounter.
?
read-only
Sensor as 32-bit Counter
Counter32
setup -> parameters -> analogInputs -> analogInpTable -> analogInpEntry -> analogInpIndex 1 to 4
replace “
?
“ with a number from 1 to 4 and “
!
” with ”1.3.6.1.4.1.38783” in the table below
OID
Name
Access
Description
Syntax
!.
8.2.2.2.1.1.2.
?
.0
analogInpDescription.
?
read-write
Analog input description
DisplayString
!.
8.2.2.2.1.1.3.
?
.0
analogInpMult.
?
read-write
Analog input multiplier x1000 in Integer format Integer32
!.
8.2.2.2.1.1.4.
?
.0
analogInpOffset.
?
read-write
Analog input offset x1000 in Integer format
Integer32
!.
8.2.2.2.1.1.5.
?
.0
analogInpMode.
?
read-write
Analog input mode - 0-10V or 4-20mA
Integer32
!.
8.2.2.2.1.1.6.
?
.0
analogInpValue.
?
read-only
Analog input value x1000 in Integer format
Integer32
setup -> parameters -> digitalInputs -> digitalInpTable -> digitalInpEntry -> digitalInpIndex 1 to 4
replace “
?
“ with a number from 1 to 4 and “
!
” with ”1.3.6.1.4.1.38783” in the table below
OID
Name
Access
Description
Syntax
!.
8.2.2.3.1.1.2.
?
.0
digInpDescription.
?
read-write
Digital Input description
DisplayString
!.
8.2.2.3.1.1.3.
?
.0
digInplowLevel.
?
read-write
Digital Input closed state
DisplayString
!.
8.2.2.3.1.1.4.
?
.0
digInphighLevel.
?
read-write
Digital Input open state
DisplayString
!.
8.2.2.3.1.1.5.
?
.0
digInpMode.
?
read-write
Digital Input mode - Discrete or Counter
INTEGER {
openclosed(0),
risingEdge(1),
fallingEdge(2),
bothEdges(3)
}