7.2.3.
Input/Output
7.2.3.1.
1-Wire sensors
For every 1-Wire sensor, a description up to 15 characters can be set.
For all sensors “Offset” field is enabled. Number from this field is used for simple correction of
displayed value.
For some specific sensor, like TSA200, TSV200 etc., fields “Unit” and “Multiplier” are also
available.
7.2.3.2.
Digital inputs
For every digital input, a description up to 15 characters can be set.
Text,
written in “Low level” and “High level” is displayed on monitoring page for this input.
These fields accept up to 15 characters.
7.2.3.3.
Analog inputs
For every analog input, a description up to 15 characters can be set.
For every analog input,
fields “Unit”, “Multiplier” and “Offset” are available. They can be used
to convert the raw voltage input to meaningful engineering units if required.
The shown value is
calculated by:
DV[Un] = (AV
–
OF) * MU
Where:
DV
–
displayed value;
Un
–
unit;
AV
–
real analog voltage from source;
MU
–
multiplier in dimension [parameter/Volt];
OF
–
offset.