The “Max” value is set far enough from the wanted temperature to avoid tr
igger/alert
conditions around it.
For every sensor or analog input, there are 3 independent ways of alert when there is an alarm
condition
–
e-mail, SNMP trap and post (HTTP/HTTPS post of XML file). Each alarm notification
method is activated by a checkbox.
Globally for all sensors and for all analog inputs, there is a checkbox
“Return notification”. If this
option is chosen there will be notification also when parameter returns in range.
Globally for all sensors and for all analog inputs, there is
“Notification delay” parameter. It is
very useful like a filter for short alarm conditions.
7.2.4.2.
Digital inputs
For every digital input, alarm state should be chosen
–
Open or Close. When the input goes in
alarm state 3 independent way of alert are possible
–
e-mail, SNMP trap, and post (HTTP/HTTPS
post of XML file). Globally for all digital inputs,
there is a checkbox “Return notification”. If this
option is chosen there will be notification also when parameter returns in range.
Globally for all digital inputs, ther
e is “Notification delay” parameter. It is very useful like a fil
ter
for short alarm conditions.
In the time when the input is in an alarm state, on Monitoring page appropriate input will be
colored in red.
There are two delays - low-to-high and high-to-low for digital input change. These delays are
added to the standard delay of 30mS. They have 100mS resolution and by default are zero.
These options can be used for additional debouncing.