TCG140_R1.1 – May 2018
Page 13
The only file stored on the mass storage is a tool called “TConfig”. This tool enables the communication
between the TCG140 and PC. After starting the TConfig tool, the following program will appear:
Pressing the “Start” button will start your web browser and display the Monitoring page of your
TCG140.
7.1.
Monitoring page
Monitoring page displays the current I/O state of TCG140
.
The page has 4 sections – “Sensors”,
“Digital inputs”, “Analog inputs” and “Relays”.
For every parameter (sensor, input, relay) there is a description of up to 15 characters. The default
descriptions can be changed in “Setup-Input/Output” menu.
The Monitoring page is automatically refreshed on 1 second.
7.1.1.
Sensors section
All detected 1-Wire sensors are shown in this section. Sensor detection is made either after
power-on or by pressing “Scan for new sensors” button. All found sensors are shown in
ascending order refer their unique ID number. For every sensor, there are a description, value,
and ID information.
All sensors have value only in the Value 1 column. Only TSH2xx temperature and humidity
sensors have the 2nd parameter shown in Value 2 column.
It is possible to lock sensors in a specific position. To do this all sensors should be added one by
one. After every addition, a new scan should be made and newly found sensor should be locked
in its position. If all sensors are locked, removing one “in the middle” will not change the
positions of following sensors after reset. This option is very useful when TCG140 is used as a
part of monitoring and control system managed by HTTP API.