
28
www.templari.com
d. DEFAULT USER / CHANGE PASSWORD
Mask Gfd01: it allows to change the password of the
acces to assistance menu.
•
Cancel history alarms: it
cancels
cmpletely the history of the alarms.
•
Insert a new password: it allows to replace
the password of the acces to the assistance
menu
G . MANUAL MANAGEMENT
This menu is protected by a password. Only the authorized staff
can have access.
Mask Gg01: It allows to force in manual (MAN) some digital
outputs so to verify the correct electrical connections.
Refers to the guide supplied with the unit for possible
other digital outputs presents
•
N05: it allows to activate the condensate drain heater.
Mask Gg02: it allows to force the van at the wanted speed,
selectable by required power.
•
Fans speed: it activates the manual management of
fans speed.
•
power required: % active if manual management is
enabled.
Mask Gg03: manual or automatic management of the
expansion valve.
•
It enables valve manual position: it enables the manual
management.
•
Valve manual position: if the manual management is
activated, it shows the opening of the valve measured in
steps.
Mask Gg04: injection valve manual or automatic
management.
•
It enables valve manual position: it enables the manual
management.
•
Manual valve position: if the manual management is
active, it shows the valve opening in steps.
Mask Gg05: manual or automatic management of the heat
pump.
•
CH/HP Request: it enables speed manual management
of compressor for the heat pump in heating and cooling.
•
speed: if the manual management is active, it shows
the compressor speed for the heat pump
Mask Gg06: it enables the defrosting cycle.
•
It enables the defrosting cycle: it enables a defrosting
cycle.
Mask Gg07: management of oil recover
•
It enables oil forcing: it enables a forcing in oil recover
cycling.
Mask Gg08: integration management.
•
N06 Plant Integr.: auxiliary heater output (es. boiler).
Mask Gg09: only in AIR version. Management of winter
fan.
•
Fan speed: it enables the manual management of fan
speed.
•
Power required: % active if it is enabled in manual
management.
Mask Gg10: this mask allows to manage screed dryer
function.
•
Start cycle: set the function ON or OFF.
•
Elapsed time: It shows the elapsed time after the
activation of the function.
• Start temperature: the starting temperature of the
function.
•
Target temperature: the traghet temperature of the
function. The temperature increases linearly.
•
Raise hours: the amount of hours the function must use
to raise from starting temperature tu target temperature.
•
Stabilise hours: the amount of hours the function must
stay in target temperature.
•
Cool down: the amount of hours the function must
use to cool down from target temperature to start
temperrature.
Mask Gg11: this mask allows to ignore the oil temperature
control of the compressor.
Maschera Gg12 initialization: this mask is used to initialize
the heat pump. The initialization erase all data previously
saved in the heat pump.
USE EXTREMELY CAREFULLY, CONTRARY THE COMPRESSOR
CAN BREAKS AND THE GUARANTEE EXPIRES.