Templari KITA AIR Installation Instruction Download Page 27

27

www.templari.com

Mask Gfc22:

• 

Enable  protection: it allow to enable or not 

the  function  winter  antifreeze  protection  that 

activates the compressors when the plate heat 

exchanger reaches a temperature too low.

Mask Gfc23: enabling external reports

• 

It enable warning reports on output NO7: it 

allows  to  enable  the  digital  output  NO7,  to 

whom it could be connected for example a 

notification led, when the machine is in alarm 

for minor causes.

Mask Gfc25: defrosting setting.

• 

Fan  consumption:  fan  consumption  in  Watt 

calculated by the electronic and used to start 

the defrosting procedure.

• 

Start up delay: start up delay of the compressor 

after that it is allowed  the defrosting start up.  

To avoid that the defrost starts just after the 

ignition  of  the  compressor,  situation  where 

you  can  have  the  conditions  of  the  defrost 

start up, due to the start up dynamics. 

• 

Fan delay: waiting time before of starting the 

defrost

• 

Defrost delay with temperature differencies: 

Waiting time for the activation of the defrost 

for delta T.

Mask Gfc27: parameters defrost.

• 

En oil defrost: element that allows to enable 

the returno of the oil through defrost cycle. If 

enabled and if the unit required the return of 

the oil normal defrost procedure is activated 

with  maximum  settable  speed  with  the 

following parameter “Defrost Speed”.

• 

Low  speed  defrost: if ate the moment of 

defrost start up the compressr had a lower 

speed than the Thershold the compressor 

speed during the defrost will be defrost speed.

Mask Gfc34: drip parameters.

• 

Drip  manag.:  it  enables  the  operation  of 

the fan before the inversion of the 4-way in 

output from the defrost cycle, that rotating at 

a high rpm promotes the disposal of the water 

drops still in the battery.

• 

Fan Dripping Speed: it is the speed where the 

fan is forced il ventilatore in this specific phase  

of the defrost process.

• 

Fan reverse Dir: it allows to enable or not the 

reversing of the rotation direction of the fan. 

If enabled, the dripping is made with a fan 

that turns in the opposite.

Mask Gfc37: defrost parameters.

• 

Integration  of  the  system  during  the 

defrosting.:  It  enables  the  integration 

generator to the system (boiler or electric 

resistance).

• 

Def.  end  max  time  exceeded: it allows 

to  choose  between  HISTORY  and 

ALARM,  that  is  to  choose  the 

registration/reporting mode of the event “the 

defrosting is finished because the maximum 

time is exceeded”.

Mask Gfc50: It allows to enable the condensate drain 

in  fix  or  intermittent    mode  in  base  on  the  external 

temperature.

• 

Res.drain cond.: it enables the activation of 

the resistance for the condensate drain.

• 

ALWAYS  ON  (Set1):  in  this  condition, 

the  resistance  is  always  active  under  this 

parameter

• 

Set: value of temperature reached that the 

resistance condensate drain is always active. 

• 

Diff: differential of temperature. When the 

xternal temperature is equal to Text= Set+Diff 

you go out form this function

• 

MODE  ON-OFF  (Set2):  in  this  condition 

the  resistance  is  activated  under  the  set,  at 

time intervals as defined from the following 

parameters.

• 

Set: value of temperature reached that the 

function is activated.

• 

Diff:  differential  of  temperature.  When 

the  external  temperature  is  equal  to  Text= 

Set+Diff you go out from this function

• 

T.On: time of on of the resistance in minutes.

• 

T.Off: time of off of the rsistance in minutes.

Mask Gfc51: limitation in power consumption.

• 

En.Watt  limit  rps: Enabling of maximum 

allowed  speed  limitation  to  compressor  for 

work of the effective consumption in watt.

• 

Thr.: maximum threshold reachable by the 

total consumption (compressor, fan, auxiliary, 

circulator, auxiliary…)

• 

Band:  Band  in  which  the  value  of  instant 

consumption  can  swing,  but  always  staying 

under the threshold set

• 

Fan: Consumtion value read by the fan. The 

reading is possible only thanks to the protocol 

od  communication  modbus  (protocol  to 

communicate)  RS  485  (physic  network 

constitued by a certain number of wires), it is 

set in one to read the effective consumption 

value

• 

Aux:  Consumption  values  of  the  auxiliaries. 

Set equal to 20 W costant.

• 

Update  time:  interval  of  time  passed  that 

you have the update, up or down, if all 

the  conditions  aloow  it,  the  variable  that 

contains the maximum speed allowed by the 

comporessor.

• 

Update  rps:  positive  or  negative  increasing 

of the variable that contains the maximum 

speed available by the compressor.

Operation: 

• 

if Thr is< the current consumption of the unit 

the  limitation  of  the  maximum  rpm    of  the 

compressor starts  decreasing of “Update rps” 

every “Update time”

• 

if the current consumtion is included between 

(Thr-Band) and Thr correction actions aren’t 

made 

• 

if  the  current  consumption  is  <  than  (Thr-

Band) the compressor is free from binds (the 

maximum speed allowed can increase)

Mask  Gfc56:  it  aloows  to  change  the  intervention 

threshold of defrosting.

• 

Model:  fan model present in the heat pump.

• 

Amp:  parameterization defrost.

Summary of Contents for KITA AIR

Page 1: ...INSTALLATION INSTRUCTION AIR TO AIR T H E H E A T P U M P...

Page 2: ...ts 8 6 3 Free spaces for the assembly 8 6 4 Choice of installation place 9 6 5 External unit mounting 9 6 6 Condensate discharge preparation 9 6 7 Correct alignment 10 6 8 Probe installation 10 7 Mont...

Page 3: ...8 12 5 Electric diagram KITA AIR 19 12 6 Internal wiring connection diagram 20 13 Commissioning 21 13 1 Preliminary controls 21 13 2 Commissioning 21 14 Control unit 22 14 1 Control panel measurement...

Page 4: ...sary please request for original parts You can find all informations on the KITA Templari label in accordance with the regulation on labeling in particular you can find Voltage and frequency of Power...

Page 5: ...supply For design and realization of the heat pump all the CE directives and all the DIN and VDE have been observed The electric connection of the heat pump must be made in accordance with the VDE EN...

Page 6: ...e indicated on the plate 1 Figure 1 and 2 figure 1 1 3 3 Operation mode The heat pump can operate in two modes actionable trough the switching of the 4 way valve as shown below this modes are heating...

Page 7: ...mension 1 Deflector 2 Fan 3 Case 4 Battery exchanger 5 Electric box 6 Side cover remove to access to electric box 7 Probe cable B2 prewired to unroll The image is intended only to indicate the main in...

Page 8: ...he provisions in force It is recommended to pay attention do not to overexertion when lifting the internal unit It is advisable to be at least in two persons 6 Mounting and installation 6 1 Equipment...

Page 9: ...are snowfalls install the heat pump at least 25 cm from the ground to avoid clogging at the inlet and drain zone 6 5 External unit mounting 1 Before installing the device please see the safety warnin...

Page 10: ...e irreparable damages to the evaporator In places where there are snowfalls install the heat pump at least 25 cm from the floor to avoid clogging in the suction and condensate drain area 6 7 Correct a...

Page 11: ...the circuit Nominal lenght Maximum lenght of the piping m of equivalent length Maximum height difference m of equivalent length Additional refrigerant charge recommended g m of equivalent length All...

Page 12: ...connect the pump charging vacuum connection procedure 1 4 inside the external unit Perform the vacuum until reaching 0 4mbr pressure duration of procedure for about 1 h for 15m total length connection...

Page 13: ...or incrustations of various kinds also provoking a malfunctioning of the heat pump It is possible then clean the battery with a under pressure jet of air in a parallel direction of the fins you should...

Page 14: ...cable The cable carries low voltage control signals find a route far from sources of interference do not joints along the way possibly using a 3 core cable shield section 1 50 sq mm shield connected...

Page 15: ...ower supply cables indication KITA AIR External unit Supply 400 Vac 50 Hz Cable 5x6 mmq Secondary line protection 230 PC protection 24 Vdc 3 fuses 5x20 4A 1 fuse 5x20 4A Internal unit Supply 230 Vac 5...

Page 16: ...E 1 3 5 7 9 11 2 4 6 8 10 12 B2 1 3 5 7 9 11 2 4 6 8 10 12 B2 Gnd B4 GND B5 VDC B3 GND Y3 GND B7 GND C 230V auxiliary power supply internal fan A Auxiliary fuses 4 A B Power Phase Neutal and Ground fo...

Page 17: ...switch high DI6 solar boost SGR bit0 DI8 remote on off DI9 P Lan protocol DI10 flow switch present on old models F4 Elektrische Sicherung 5x20 250 mA Y2 Y3 PWM Circulator GND 5VR C4 NO8 NO9 NO10 NO11...

Page 18: ...alve 14 Block outputs C1 NO1 NO3 15 Block outputs C2 NO4 NO6 16 Block outputs C3 No7 Nc7 17 Block outputs C4 NO8 NO12 18 Bar hooks Din 35 6 1 2 3 4 5 9 7 8 17 10 11 12 13 14 15 16 18 18 18 12 1 Digita...

Page 19: ...IDC2 J8 J10 J12 J13 J14 J15 J1 5 J 4 J 3 J 2 J J18 J16 R S T N R S T N N EVV EVV M OUT 5vrf M OUT 5vrf R S T Heater condensate drain Injection valve 4 4 CH 3 RS485 M 3 M 3 RS485 Bridge to the terminal...

Page 20: ...2 1 N Lok 6 Yellow Green N Blue T Brown N Blue N Blue NO11 6 5 4 3 2 1 N Lok 9 Brown PE Yellow Green No10 Brown 8 7 9 20 19 B6 B1 14 13 12 11 10 9 Molex Mini Fit Jr 20 White 5V Red Gnd Black B11 B10 W...

Page 21: ...y the proper operation Access to menu D inputs outputs to control the different temperatures from sensors Screen D01 B1 it shows the value of liquid sub cooling in the heat pump it has to stay in a ra...

Page 22: ...ivation It activates when the solar panels are installed and active It activates when the defrosting procedure is active 4 Unit status The unit can be in one of the following states OFF ON ENERGY S AU...

Page 23: ...20 percentage points Those conditions permit to work with a noisiness more and more reduced We underline that setting this function the efficiency of the machine too is progressively reduced Mask B06...

Page 24: ...the other days press and proceed as explained above Contrary it is possible to copy the setting in different days once entered in mask C02 press the button to have access to the choice of the day you...

Page 25: ...ating DSH Discharge Super Heating Mask D19 Parameters Inverter Engine Mask D20 Parameters Inverter Engine Mask D21 Parameters Inverter Engine Masks D30 D31 masks relevant to the external battery fan Y...

Page 26: ...ion is active OFF Propor it s the percentage of the proportional band Hc06 that as defaut is set at 10 under that the integration shut down OFF Diff Degrees the integration has to produce more on Setp...

Page 27: ...the defrosting is finished because the maximum time is exceeded Mask Gfc50 It allows to enable the condensate drain in fix or intermittent mode in base on the external temperature Res drain cond it e...

Page 28: ...bles speed manual management of compressor for the heat pump in heating and cooling speed if the manual management is active it shows the compressor speed for the heat pump Mask Gg06 it enables the de...

Page 29: ...ors D06 Analog sensors D07 Fan speed Circulator speed D08 Cooling circuit status D09 Work regime D10 Work pressures D11 Work pressures D14 Drain Gas Control D15 EED set up D19 Inverter Engine paramete...

Page 30: ...A12 Probe B12 broken or disconnected Automatic 60 sec Yes Stop the machine ALB01 Position ID3 High pressure Manual Immediate Yes Stop the machine ALB02 High pressure of the compressor 1 from transduce...

Page 31: ...e Immediate Settable Gfa01 Only signal ALT08 Threshold reached worked hours outside battery fan Manual Immediate Settable Gfa01 Only signal ALU01 Geothermal frosting protection exchanger Manual par Gf...

Page 32: ...of time the cause can be the inertia of the system and the nearness between the temperatures of air and water If it occurs occasionally it s just a no serious signal permitting to the unit to keep on...

Page 33: ...umer 1 Nominal diameter mm 910 Maximum input power kW 0 625 Maximum current A 1 1 Max speed rps 610 Max air flow m3 h 15000 Internal fan Model EBMPAPST Type Inverter BLDC Numer 1 Nominal diameter mm 8...

Page 34: ...ate Applied standard Standard Armonizzati EN 55014 1 2006 A1 2009 EN 55014 2 1997 A 2001 A2 2008 EN 61000 3 2 2006 A1 A2 2009 EN 61000 4 2 2008 61000 4 4 2008 EN 61000 4 5 2008 EN 61000 4 6 2008 Angew...

Page 35: ...Note...

Page 36: ...vers 26 07 2019 C via Pitagora 20A 35030 Rubano PD Italia Tel 39 049 8597400 39 049 5225929 www templari com info templari com T H E H E A T P U M P...

Reviews: