11.3 pLAN web wiring - “multi-KITA”
If the air conditioning system has more units which interact with
each other in a pLAN logical “master-slave”, you need to connect
the machines via the bipolar cable screened according to the
following scheme:
Scheda 1
(master)
Tx+
Tx+
Tx+
Tx+
tx-
tx-
tx-
tx-
GND
GND
GND
GND
Scheda 2
Scheda 3
Scheda 4
The wiring should be done in the port dedicated to the “P-2 LAN”
tab (see point 11 on the scheme in chapter 12).
12 Electronics (UPC)
1
Power 24 Vdc
2
Sensor power
3
Analog inputs from B1 to B7
4
Port BMS
5
Digital inputs from DI1 to DI7
6
Analog outputs from Y1 to Y4
7
Analog inputs from B8 to B12
8
Injection valve
9
Digital inputs from DI8 to DI12
10 P-Lan 1 Operator panel
11 P-Lan 2
12 Port RS485 Modbus
13 Expansion valve
14 Block outputs C1 NO1 - NO3
15 Block outputs C2 NO4 - NO6
16 Block outputs C3 No7 - Nc7
17 Block outputs C4 NO8 - NO12
18 Bar hooks Din 35
6
1
2
3
4
5
9
7
8
17
10
11
12
13
14
15
16
18
18
18
12.1 Digital outputs
KITA AIR
NO1
/
NO2
/
NO3
/
NO4
/
NO5
Condensate discharge heater
NO6
alternative power source
NO7
/
NO8
/
NO9
/
NO10
4 way valve for cycle inversion
NO11
Compressor carter heater
NO12
/
12.2 Digital inputs
KITA AIR
ID1
Winter/Summer commutation
ID9
Thermic compressor discharge
ID3
Pressure switch for high pressure
ID4
/
ID5
/
ID6
/
ID7
/
ID8
Remote on-off
ID10
Flow switch
12.3 Analogical outputs
KITA AIR
Y1 (0-10V)
/
Y2 (0-10V)
/
Y3 (0-10V/PWM)) /
Y4 (0-10V)
/
12.4 Analogical inputs
KITA AIR
B1 (NTC HS)
B2 (NTC)
Internal ambient temperature
B3 (NTC)
B4 (NTC)
B5 (NTC)
B6 (0-5V)
Injection pressure transducer
B7 (NTC)
B8 (NTC)
External temperature
B9 (NTC HT)
Compressor discharge temperature
B10 (NTC HS)
Compressor suction temperature
B11 (0-5V)
High pressure transducer
B12 (0-5V)
Low pressure transducer