START-S3XL
Technical Manual
-9-
2.13 Connection of the “START” and “PEDESTRIAN” commands
The PEDESTRIAN opening command can be connected to any push-
button or N.O. (normally open) contact. If several devices are used,
they must be connected.
Using terminals 9 and 16 it is possible connect a TIMER to program
gate opening. The timer contact must be an NO (normally open) con-
tact and must remain closed for as long as the gate remains open.
If an opening command is connected to terminal 16, it must be con-
nected in parallel.
The START opening command can be connected to
any push-button or N.O. (normally open) contact.
2.12 Connect the 3 WIRES PHOTO-BEAM
POWER SUPPLY
TX PHOTOCELL
POWER SUPPLY
RX PHOTOCELL
+
-
+
-
Photocell receiver.
N.C. contact terminals
-
+
Bring JUMPER AC/DC
as shown in the picture
Voltage:
24 Vdc
Maximum current:
300 mA
The TEST light signals that the internal logic is functioning correctly. It must fl ash at one second intervals indicating
that the internal microprocessor is on and awaiting a command. When the control unit is powered, the warning
lights, set on the inputs, are ON when the contacts on the inputs are closed toward the common:
Normally the red lights on inputs
STOP - PHOTO - LSO - LSC - STOP - ALT
are
ON
Normally the green lights on the control inputs
START - PEDESTRIAN
are
OFF
STOP PHOTO LSO LSC START PED
ALT
Safety edge
2.14 Checking connections
8 9 10 11 12 13 14 15 16 17 18 19
8 9 10 11 12 13 14 15 16 17 18 19