telsiu altas START-S3XL Instruction Manual Download Page 14

START-S3XL

Technical Manual

-14-

5.2 

Times learning with the “PEDESTRIAN” COMMAND

The PEDESTRIAN command is used to open the automation only partially to allow people and small vehicles to 

pass through without having to open the gate completely. 

When opening is performed with this command, the 

automation decelerates only when it is closing and following the setting previously acquired in the START 

command programming.

1

Set switch 

DIP 1 

to

 ON

The automation 

is in the CLOSED 

position

               

Control unit power supply. (The TEST light is off when 

the control unit is in programming mode)

3

Press the PEDESTRIAN command (everything con-

nected to input 17 or the 2nd channel of the compatible 

remote control that has been learned)

The automation 

starts in 

OPENING mode

4

Press the PEDESTRIAN command to stop the automa-

tion at the desired point (end of partial opening).

The automation 

STOPS

5

Let the time elapse during which the automation must 

remain open.

This is the 

automation

“PAUSE TIME”

6

Press PEDESTRIAN command to start closing

The automation 

starts in

CLOSING mode

7

Wait for the automation to stop automatically

The automation 

is in the CLOSED 

position

8

Set the switch DIP 1 to OFF to return to normal opera-

tion. The fl ashing light goes off and the TEST light goes 

back on.

Time programming 

has been completed

4

ON

2

1

4

3

5

ON

2

1

4

3

5

5.3 

Regulating of the MOTOR FORCE

The electronic circuit board has 7 different levels of force. To decrease the motive force, press the push-button 

P on the Circuit board while the motor is running and then release it. Working down, once the 1st level has been 

reached, the unit cycles back to the 7th level. Each time the push-button is pressed, the force is decreased. When 

the force is at the lowest level, if the push-button is pressed again, the force returns to the maximum level. Passing 

from minimum to maximum level is indicated by the TEST light which goes on for a more an extended period of 

time.

7

6

5

4

3

2

1

Force level after each

time the push-button 

is pressed

The operation can only be performed while the motor 

is running. This control unit has AUTOMATIC BREA-

KAWAY. Each time the motor starts up, the electro-

nic circuit board keeps the motor force for 2 seconds 

maximum

!

L1

Summary of Contents for START-S3XL

Page 1: ...4 15 16 17 18 19 230 Vac 230 Vac Lamp Lamp MOT common MOT close MOT open Antenna Com 1 and Antenna Com 2 12 24Vdc 12 Vdc STOP FOTO LSO LSC START Pedestrian 24 Vac 24 Vac dc 20 21 Light Fototest Light...

Page 2: ...scription 1 2 Field of application 1 3 Type of installation 1 4 Technical features 2 Installation 4 2 1 Diagram of the control unit and electrical connections 2 2 Description of the electrical connect...

Page 3: ...one of the possible applications for this control unit The risks inherent to the MACHINE and the user s requirements must be analyzed in depth in order to establish how many elements need to be insta...

Page 4: ...ncreases pause time 2 1 Diagram of the control unit and electrical connections 2 Installation Connection of the VOLTAGE line 230 Volt Single phase alternate current The control unit power supply line...

Page 5: ...for all inputs services safety devices coaxial antenna braid Com2 12Vdc 10 Output 12 24 Vdc See Phar 2 6 Common 2 12Vdc 11 Output 12 Vdc maximum current 50mA positive Stop 12 STOP input Foto 13 Input...

Page 6: ...4 3 6 5 8 7 10 9 12 11 If you plan to use the photocells test or a 24V light this connection cannot be used 2 5 Connection of the COURTESY light LIGHT 230 Vac DIP 4 OFF ON CTS 2 1 4 3 6 5 8 7 10 9 12...

Page 7: ...input is NOT used put the DIP 5 on ON If the input SAFETY EDGE is not used make a link 22 23 2 8 Connection of LIMIT SWITCHES LSO and LSC The gure shows the connection of both limit switches however o...

Page 8: ...must repeat the times learning operation with the START com mand The TEST function is compatible with lower devices for example TRANSCEI VER so the gate can have a delay when opening The TEST can be d...

Page 9: ...Connect the 3 WIRES PHOTO BEAM POWER SUPPLY TX PHOTOCELL POWER SUPPLY RX PHOTOCELL Photocell receiver N C contact terminals Bring JUMPER AC DC as shown in the picture Voltage 24 Vdc Maximum current 30...

Page 10: ...stop close stop logic Closes again automatically at the end of the pause time 3 OFF closes again when turned on A complete opening pause and closing cycle is run ONLY if the au tomation is in the open...

Page 11: ...OMPLETE ROLLING CODE FUNCTION PRESS THE BUTTON WHEN YOU ARE LEARNING THE PARTIAL OPENING COMMAND THE L E D WITH PARTIAL ROLLING CODE WILL FLASH ONE TIME WHILE WHILE WHEN THE ROLLING CODE IS COMPLETE T...

Page 12: ...le to delete a single wireless control code ON 2 1 4 3 5 P L1 5 Turning on and programming the unit When the electronic circuit board is turned on if everything has been connected properly the red TES...

Page 13: ...RT to start closing The automation starts in CLOSING mode 8A On SLIDING press START to de ne the point in which the automation is to start decelerating The automation DECELERATES 8B On SWINGING withou...

Page 14: ...start closing The automation starts in CLOSING mode 7 Wait for the automation to stop automatically The automation is in the CLOSED position 8 Set the switch DIP 1 to OFF to return to normal opera ti...

Page 15: ...ns PROBLEM The electronic circuit board does not work the TEST signal light does not ash SOLUTION Check the 4A and 160mA fuses PROBLEM The 160mA fuse is burnt out SOLUTION Check the connections and ma...

Page 16: ...rtain voltage limits Reference to harmonized standards EN 60335 1 2004 108 CE EEC DIRECTIVE 2004 108 CE ISSUED BY THE EUROPEAN COUNCIL on December 15 2004 harmonizing the legislation of the member cou...

Reviews: