![telsiu altas START-S3XL Instruction Manual Download Page 15](http://html1.mh-extra.com/html/telsiu-altas/start-s3xl/start-s3xl_instruction-manual_1084360015.webp)
START-S3XL
Technical Manual
-15-
5.4
Increasing the PAUSE time
The pause time can be increased without having to repeat the times learning operation. While the automation is in
pause mode, each time the push-button P is pressed the pause time is increased by 5 seconds. The level can be
increased four times. The fi fth time the push-button is pressed, the pause time returns to the initial value (the TEST
light goes on for a more an extended period of time). Therefore, it is possible to increase the pause time by up to 20
seconds (e.g. pressing the button 4 times x 5 seconds each). If 20 seconds is not enough, it is possible to continue
increasing the pause time by performing another opening cycle.
Time variation
each time the
button is pressed
+ 5s
+ 5s
+ 5s
+ 5s
Initial time
5.5
RESET of the CONSTRUCTION SETTING UP
It is available the reset of the construction setting up:
4
4
ON
2
1
4
3
5
ON
2
1
4
3
5
The operation can only be performed
when the automation is in pause mode
during opening
!
L1
1
Put
DIP1
in
OFF
2
Keep pressed the button
P
until the led is fl ashing faster.
3
Put
DIP1
in
OFF
again
6
Problem solutions
PROBLEM:
The electronic circuit board does not work (the
TEST signal light does not fl ash).
SOLUTION:
Check the 4A and 160mA fuses.
PROBLEM:
The 160mA fuse is burnt out.
SOLUTION:
Check the connections and make certain that the
total power absorbed by the accessories does not
exceed 500mA.
PROBLEM:
The 4A fuse is burnt out.
SOLUTION:
Check the connections and the motor function,
fl ashing of the courtesy light.
PROBLEM:
The motor stops or nearly stops after a few seconds.
SOLUTION:
Try to increase the motive force (see chap. 5.3).
PROBLEM:
When deceleration is used, the automation does not reach the
rabbet.
SOLUTION:
Try to increase the deceleration rate (switch 11 and 12 of DIP).
PROBLEM:
The electronic circuit board does not perform opening.
SOLUTION:
Check the status of the red connection lights. Normally they must
all be on. If limit switches are used, the “limit switch closed” light
is off if the gate is closed. On the other hand, the green lights are
normally all off.
PROBLEM:
The electronic circuit board performs irregularly.
SOLUTION:
Make certain that the service and the safety device connections
have not been incorrectly connected to a power supply voltage
pole. IMPORTANT!! If connection is made to photocells with only 3
wires, it is best to use the 12 Vdc power supply present on termi-
nals 10 and 11. (see chap. 2.6)