56050301 – Rev B
14
© 2017 Telguard
At this point reconnect the Telco line to the TG-4’s gray jack that goes to the incoming Telco
connection at the premise.
S
TEP
5: C
ONNECT
S
UPERVISORY
T
RIP
O
UTPUTS
Connect and test the supervisory trip outputs to the alarm panel.
Enabling of a local alarm or strobe light may be desirable when a trip is declared. The STC trip
output can be used directly to activate a local signaling device, provided that the trip output is not
needed to trip the host control/communicator at the same time. If both a local signal and a control trip
input are required, then external relays are needed to provide additional uncommitted contacts.
NOTE: UL Listed installation of the TG-4 will at a minimum have the trip output to the alarm
panel to indicate low AC (ACFC) and low battery (LBC) conditions.
R
EPROGRAM
A
LARM
P
ANEL TO
S
END
P
ROPER
C
ODE
If necessary, reprogram the alarm panel to send proper alarm code when tripped by the Telguard’s
supervisory output. Program zone restoral as desired.
C
HECK
P
ROPER
O
PERATION OF
T
ELGUARD
S
UPERVISORY
O
UTPUT
Check for proper operation of each programmed supervisory output by causing it to trip the alarm
panel and making sure the proper LED illuminates and that the proper trouble code is reported to the
central station. Skip the testing of any supervisory functions that have not been enabled. Note that
the yellow MODE LED 3 starts to flash when the alarm panel goes off-hook to report the alarm signal
over cellular.
Low Battery Condition (LBC)
: Disconnect the battery and during the next 60 seconds
check to see that the STC LED 2 flashes 2 times indicating that the battery is missing.
Check to see that the alarm panel indicates the STC trouble code on the STC LED.
Reconnect the battery and check during the next 60 seconds to see that the STC LED 2
goes off, indicating the missing battery condition has been restored.
Line Fault Condition (LFC):
Disconnect Telco cable from the gray jack. LED 2 flashes 3
times and after 60 seconds the panel transmits the STC trouble code (over cellular) to the
central station indicating the incoming Telco line is disconnected. Reconnect Telco cable
and check to see that the STC LED 2 goes off in 30/60-seconds indicating Telco line
restored.
No Service Condition (NSC
): Disconnect the antenna from the Telguard. Check to see
that the STC LED 2 flashes 4 times in 60 seconds and the alarm panel transmits the STC
trouble code over the Telco line indicating loss of cellular registration. Reconnect the
antenna and check to see that the STC LED 2 goes off within 30/60 seconds indicating
cellular registration has been restored.
AC Fail Condition (ACFC)
: Disconnect the 12VAC, 10VA transformer and check to see
that the AC POWER LED goes out and the STC LED 2 flashes once indicating that AC
power is missing. Reconnect the AC transformer and check to see that the AC POWER
LED goes on and the STC LED 2 goes off indicating that AC power has been restored. No
transmissions will be sent to the central station. The AC power must be off, continuously,
for 2 hours before the STC relay causes the alarm panel to send a trouble code.