System Status LEDs Table
System Status LEDs
Activation Indications
LED 1-5 FLASHING
Failed Activation – Signal Too Weak
LED 1 & LED 4 FLASHING
Activation Error – Call Telguard Technical Support
LED #1 ON
Activation Successful
System Trouble Condition, STC (LED 2) Table
Status LED 2
Indication
1 FLASH
ACFC - AC Low or Missing
2 FLASH
LBC – Low Battery and/or Battery Charger Failure
3 FLASH
LFC – Line Fault
4 FLASH
NSC – No Service
5 FLASH
RFC – Radio Failure
6 FLASH
DTF – Dial Tone Failure
7 FLASH
PPF – Panel Presence Failure
C
ONNECT
A
LARM
P
ANEL TO
T
ELGUARD
B
LACK
J
ACK
Plug the modular jack of the alarm panel to black jack on the Telguard.
V
ERIFY
A
LARM
S
IGNAL
T
RANSMISSIONS OVER
C
ELLULAR
Before beginning this step, disconnect the Telco line from the TG-4’s gray jack that goes to the
incoming Telco connection at the premise.
Trip several alarms on the alarm panel and verify that the central station received them by calling the
central station operator. Use a lineman's butt-set in
MONITOR MODE
connected to Telguard's "T"
and "R" test pins to "listen" to communications between the alarm panel and Telguard.
If you are having problems getting reliable alarm signal transmissions, additional adjustments may be
necessary.
Recheck signal strength. You need
RSSI = 2½
(TWO LEDS ON SOLID AND THE THIRD
LED FLASHING)
for adequate signal transmission. Also, check antenna connector and
make sure it is seated correctly.
Call Telguard Technical Support, 1-800-229-2326 extension 9
.