MULTIXPLO AND MULTITOX DETECTORS
OPERATING MANUAL
48
NOSP17665
Revision 02a
If the detector enters in ambiguity mode, a test of the zero point and a gas test are recommended.
We recommend cleaning the communication head window at the same time.
For any other operation, please contact your supplier or our technical services.
7.2.2
Corrective maintenance
If the detection unit or the PLC signals a detector’s fault, the detector must be tested directly with
the wireless communication tool to determine the type of fault.
If the detector is configured in 0-22 mA output, it is possible to have a pre-diagnostic of the fault.
7.3
List of main faults
In addition of the current loop faults, other information are available from the wireless
communication tool TLU600 (refer to § 6.6). If the detector does not work properly, the following
table can help you to determine the causes and effects of different possible troubles
.
FAULTS
CAUSES
SOLUTIONS
Backlight display
switched off
Power supply failure
Check the power supply (18 and 35
V
DC
) at the detection unit or the PLC
output
Continuity issue
Check line continuity
No 4-20 mA / 0-22
mA signal
3-wire cabling
Power supply failure
Check the power supply (18 and 35
V
DC
) at the detection unit or the PLC
output
Continuity issue
Check line continuity
No shunt between V+ and L+ Place the shunt
No 4-20 mA / 0-22
mA signal
4-wire cabling
Power supply fault
Check the loop with an ammeter.
ZERO_FAULT
(Zero point fault)
Zero-point resetting
impossible
Fault memorized, even on a power
supply shut down. To acknowledge
this fault, make a full calibration (in
general, the sensor needs to be
replaced).
Summary of Contents for Everywhereyoulook DG-TT7-K
Page 18: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 12 NOSP17665 Revision 02a...
Page 34: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 28 NOSP17665 Revision 02a...
Page 58: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 52 NOSP17665 Revision 02a...
Page 66: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 60 NOSP17665 Revision 02a...
Page 68: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 62 NOSP17665 Revision 02a...
Page 69: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 63...
Page 70: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 64 NOSP17665 Revision 02a...
Page 71: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 65...