MULTIXPLO AND MULTITOX DETECTORS
OPERATING MANUAL
NOSP17665
Revision 02a
39
6.8.2.2
Calibration
Calibration must be made with the gas the detector is set to detect, with the SET menu (F2 key) of
the wireless communication tool TLU600 and a calibration kit. The calibration gas should be
injected at a flow rate between 30 l/h and 60 l/h.
The detector is in maintenance inhibition mode for 10 minutes after it goes back to main screen.
Use the setting menu and validate the INH command for acknowledgement.
To end of communication between the TLU600 and the detector is done by pressing F4 key on
main menu.