MULTIXPLO AND MULTITOX DETECTORS
OPERATING MANUAL
26
NOSP17665
Revision 02a
The table below shows the maximum cable lengths based on the wire cross section:
Min. single wire cross section mm²/AWG 0,5 (20) 0,9 (18) 1,5 (16) 2.5 (13)
Maximal Length
/
15 m
30 m
50 m
4.4
Detection cartridge
The cartridge is separated from the detector to enable its replacement. Its dismantling is extremely
easy and does not need to touch the rest of the unit.
Caution during the assembly and the disassembly of the cartridge on the detector:
Slide the positioning pin of the cartridge into the corresponding hole in the housing
(at the bottom of the receiver).
Take care to not damage the cartridge connector when tightening the two parts.
This operation imperatively requires power to be off
Loosen the locking screw on the side of the nut (see Figure 1),
then unscrew the nut, along the first part of the thread. With the
nut, pull on the cartridge to remove it and then unscrew the
cartridge from the nut.
Cartridges have an identification colour ring (see §1.4).
Insert a new cartridge of the same colour into the case
respecting the position defined by the centring pin, screw the
nut until it stops ensuring the presence of O-ring. Then, tighten
the locking screw.
Switch on the device in order to make the calibration of the new cartridge and the zero
adjustment.
Summary of Contents for Everywhereyoulook DG-TT7-K
Page 18: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 12 NOSP17665 Revision 02a...
Page 34: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 28 NOSP17665 Revision 02a...
Page 58: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 52 NOSP17665 Revision 02a...
Page 66: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 60 NOSP17665 Revision 02a...
Page 68: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 62 NOSP17665 Revision 02a...
Page 69: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 63...
Page 70: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 64 NOSP17665 Revision 02a...
Page 71: ...MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a 65...