Page 52
Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2011 Telect, Inc., All Rights Reserved, 139249-1 A0
2. Making sure each Phillips screw is lined up with the hole in the chassis, screw each one in
until the rectifiers are firmly seated in the chassis.
WARNING
!
WARNING! Make sure the circuit breakers are turned OFF before installing the modules.
Note in the following figure that you can see the WHITE post under the breaker button.
WARNING
!
WARNING!
3. Slide the MDS modules into the MDS slots at Layer 1, starting with the slot next to the GMT
module in slot 1.
The MDS modules are uniquely designed for circuit breakers and GMT circuits. Installers can
configure MDS modules as necessary for a given site.
To insert the MDS module (with breaker installed per the installation instructions included
with each MDS module you receive),
GFI
Heater
Slot 1(GMT) Slot 2 Slot 3 Slot 4
Layer 1:
Layer 2:
Layer 3: AC
Layer 4: DC
Layer 5: Front-access
Power Termination
6 5 4
1 2 3
Figure 57 - DC Power System
MDS modules
Rectifiers
Distribution Panel
Controller Shelf
Shelf
Figure 58 - Rectifier Breakers Shown Turned OFF