Installation Instructions
18
RM4000 Rackmount Kit
b.
Select mounting method according to rack type:
H
To mount the slide-out tracks with their front and rear flanges
outside of the front and rear rails, use the mounting method A shown
in Figure 12 when doing substep c. Add a bar nut to the installation
only if the rails have untapped holes.
H
To mount with front and rear flanges inside of rails, use the
mounting method B outlined in Figure 12. This mounting method
assumes untapped holes.
c.
Install in rack:
Using the method and hardware determined from substep
b, secure the right slide-out track assembly to its front and rear rails. The
screws should be fully, but lightly, seated so mounting can be adjusted
later.
d.
Fix the length of the slide-out track assembly:
Tighten the screws,
applying 28 inch-lb of torque, left loose in step 1, substep c to fix the
front to rear flange spacing of the slide-out track assembly.
e.
Mount the left slide-out track assembly:
Repeat substeps c through d to
mount the left slide-out track assembly.
Mounting Method A
Mounting Method B
Left-front
rack rail
Use two flat-head screws if the cabinet rails have
countersunk mounting holes; otherwise use two
pan-head screws
Use a bar nut if front rails
are not tapped
10-32 Flat-head
screws (4)
10-32 Pan-head
screws (4)
10-32 Pan-head
screws (4)
Left-front
rack rail
# 10
M6
M5
English
Metric
# 12
Outer track
Front flange
Outer track
Front flange
Use a bar nut
Figure 12: Installation of slide-out track assemblies in rack (top view)