VOT 2; Rev 1.2; EN; 09.07.2013
TKT67C
– Installation and maintenance
6
3.5 List of optional features
For more information on optional features, see Chapter
TST6731
Integrated Printer TKT67xxC
TST6732
LCD Display Module TKT67xxC
TST6741
Extra Charger Module (adds power taken from mains 3,000 VA)
(1-2 pcs each 3,000 VA, Max each 180 Ah) TKT67xxC
XWT6772
Switched-Maintained Package for 16 circuits each 350 W TKT6716C
XWT6773
Switched-Maintained Package for 24 circuits each 350 W TKT6724C
XWT6774
Switched-Maintained Package for 32 circuits each 350 W TKT6732C
XWT6775
Switched-Maintained Package for 40 circuits each 350 W TKT6740C
XWT6776
Switched-Maintained Package for 48 circuits each 350 W TKT6748C
XWT6777
Switched-Maintained Package for 56 circuits each 350 W TKT6756C
TST6751
IC Interface for 8 circuits each 350 W TKT6708C
TST6752
IC Interface for 16 circuits each 350 W TKT6716C
TST6753
IC Interface for 24 circuits each 350 W TKT6724C
TST6754
IC Interface for 32 circuits each 350 W TKT6732C
TST6755
IC Interface for 40 circuits each 350 W TKT6740C
TST6756
IC Interface for 48 circuits each 350 W TKT6748C
TST6757
IC Interface for 56 circuits each 350 W TKT6756C
Central monitoring options:
TST6722
LON Interface TKT67xxC
TST6701
BACnet Interface TKT67xxC
TST6721
ACM Interface TKT67xxC
TST6724
WebCM/ WebACM Interface TKT67xxC
TST1811E
BCM Interface TKT67xxC
3.6 General description
TKT67xxC(N) central battery unit is designed and manufactured according to the standards EN 50171
and EN 60439-1.
In normal situation, the central battery unit operates using a 230 V AC mains voltage, maintaining the
battery charge level and supplying a voltage of 230 VAC to the maintained output circuits. If the mains
voltage is interrupted or it drops below 180 V, the central battery unit switches to battery use. This
connects a voltage of 220 VDC to the non-maintained circuits and the voltage supply to the maintained
circuit switches from 230 VAC to 220 VDC. The battery supply is used as long as the mains voltage
remains unavailable or the battery voltage has dropped to the deep discharge limit (173 V).
In addition to the above mentioned standard functions, the control unit of the central battery unit also
includes the following monitoring, testing and reporting functions:
testing the luminaires either through addressable monitoring or by measuring the circuit
current and by monitoring the condition of the batteries
testing the capacity of the battery
Summary of Contents for TKT6716C
Page 26: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 26 5 2 1 Parts layout...
Page 42: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 42...
Page 43: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 43...
Page 44: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 44...
Page 45: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 45...
Page 46: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 46...
Page 47: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 47...
Page 48: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 48...
Page 49: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 49...
Page 50: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 50...
Page 51: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 51...
Page 52: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 52...
Page 53: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 53...
Page 55: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 55...