VOT 2; Rev 1.2; EN; 09.07.2013
TKT67C
– Installation and maintenance
22
shown on the display.
If luminaire test will not start, check
battery voltage level. It must be
more than
200 VDC.
LOCAL CONTR.
ALARM
The central battery unit can be remote
controlled to send a local controller pulse to all
circuits, in which case all the non-maintained
addressable luminaires (Teknoware types
ending in K, or external luminaires fitted with
Teknoware address module) that are
connected to the central battery unit are
switched on. This feature can be activated by
opening loop 68-69.
If the LED is lit, the loop 68-69 is open.
If the LED is blinking slowly, K model
luminaires are turned on from the menu
with AC voltage.
.
Check the loop between connectors
68-69.
FUSE FAULT
If the LED is lit, there is a faulty fuse in the
control module.
If the LED is blinking slowly, there is a
faulty fuse in the circuit shown on the
display.
If the LED is blinking quickly, there is
some other fault in the circuit shown on
the display.
Check all circuit output fuses.
EXTERNAL FAULT
Alarms when an external fault is detected in
the luminaire or the luminaire test has
detected an error.
If the LED is flashing with
Luminaire test
LED,
configuration is in progress.
Check that all luminaires are
working.
INTERNAL FAULT
If the LED is lit continuously, there is a fault in
the battery or charging circuit. i.e. the alarm is
coming from the Central Module, or the
battery test has detected an error.
If the LED is flashing, there is a fault in a
circuit output fuse or output circuit
Check if battery or charger is faulty.
Measure voltage level of batteries.
In normal situation it should be
243-255 VDC.
Summary of Contents for TKT6716C
Page 26: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 26 5 2 1 Parts layout...
Page 42: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 42...
Page 43: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 43...
Page 44: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 44...
Page 45: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 45...
Page 46: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 46...
Page 47: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 47...
Page 48: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 48...
Page 49: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 49...
Page 50: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 50...
Page 51: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 51...
Page 52: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 52...
Page 53: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 53...