APPENDIX 1: Report Layout
Title information
CENTRAL BATTERY UNIT 01 00.00.2010
00:00
CIRC. LUMINAIRE MONITORING A B C D mA
The input current of the circuit
01-Lo OOOO OOOO OO.. .... _ _ _ _ 360
02-Lo OOOO OOOO OO.. .... _ _ _ _ 380
03-Lo OOOO OOOO OO.. .... _ _ _ _ 390
04/Lo .O.. .... .... .... _ _ _ _ 320
05-Lo OOOO OO.. .... .... _ _ _ _ 470
06-Lo .OOO OO.. .... .... _ _ _ _ 400
07-Lo OOOO OO.. .... .... _ _ _ _ 430
08-Lo OOOO OO.. .... .... _ _ _ _ 440
CIRC. CIRCUIT MONITORING A B C D mA
09-P- ...O OOOO OOOO OOOO _ _ _ _ 360
10-P- ...O OOOO OOOO OOOO _ _ _ _ 380
11-P- ..OO OOOO OOOO OOOO _ _ _ _ 390
12-P- .... .OOO OOOO OOOO _ _ _ _ 310
13-P- OOOO OOOO OOOO OOOO _ _ _ _ 460
14-P- ..OO OOOO OOOO OOOO _ _ _ _ 390
15-P- .OOO OOOO OOOO OOOO _ _ _ _ 420
16-P- .OOO OOOO OOOO OOOO _ _ _ _ 420
Lo = addresses 1-16
P = Circuit monitoring
In circuit monitoring the strength of the current is
shown from right to left
DISCHARGE CURR. 01.20A
Current of all circuits in battery use
BATT. VOLTAGE 249V
Voltage of battery on time of printing
LUMINAIRE TEST OK 00.00.00
Result and date of last luminaire test
BATTERY TEST OK 00min 00.00.00
Result and date of last battery test
SYSTEM TEST OK
Fault in central module, battery or charging circuit
SETTING
Auto conf 1 A=Local Contr.1
Automatic configuration ON
Test Selection 1/1 B=Overload
Test Selection 1/1 = Gap between test dates /
selected automatic tests
Sensitivity 080mA C=Fuse
Current-range of circuit monitoring
Test Duration 24:00 D=Output Switch
Selected time of day for luminaire test
Connect. Delay 00min O=OK
Selected connection delay from battery use to
mains use
Battery Level 210V #=Faulty
Voltage with which automatic battery test will be
stopped
Operation time 060min
Operation time of the central battery unit
STATUS 110800emd
Status message tells the status of the unit
Symbol explanations:
A= Local Controller Fault
O = OK
B= Circuit Overload
# = fault
C= Fuse Fault
D= Output Circuit Fault
? =Unknown luminaire (added, automatic configuration
not in use
= Luminaire not connected
The condition of the fuses is monitored in real-time on mains operation. Blown fuses can be detected if there
is any load on the circuit. Empty circuits are not inspected.
NOTE! Only maintained circuits can be monitored in real-time (MODE closed). An internal error alarm on a
fuse error will be given as soon as the error is detected. The error information will be automatically reset when
the fuse has been replaced with a new one.
Summary of Contents for TAPSA CONTROL TKT65
Page 43: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 43...
Page 44: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 44...
Page 45: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 45...
Page 46: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 46...
Page 47: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 47...
Page 48: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 48...
Page 49: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 49...
Page 50: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 50...
Page 51: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 51...