VOT 34; Rev 1.81; EN; 11.12.2019
TKT65C
– Installation and maintenance
21
INTERNAL FAULT
If the LED is lit continuously, there is a fault in
the battery or charging circuit. i.e. the alarm is
coming from the Central Module
If the LED is flashing, there is a fault in a
circuit output fuse or output circuit
Check if battery or charger is faulty.
Measure voltage level of batteries.
In normal situation it should be
243-255 VDC.
4.10
Buttons
MENU / OK
Used for selecting a menu or accepting a selection.
Used for starting tests and/or printing.
BROWSE
Used for browsing menus and making selections within the menu.
SET
Used for changing a desired setting in the menu.
Press for 3 seconds to start luminaire test.
Press for 8 seconds to start battery test.
1 s V-METER
Press and hold SET for 1 second: the voltage of the battery is displayed in the
LCD display
2 s DC A-METER
Press and hold SET for 2 seconds: DC discharge current from the battery
4 s LUMIN. TEST
Press and hold SET for 4 seconds: start of the luminaire test
6 s BATT. TEST
Press and hold SET for 6 seconds: start of the battery test
Summary of Contents for TAPSA CONTROL TKT65
Page 43: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 43...
Page 44: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 44...
Page 45: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 45...
Page 46: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 46...
Page 47: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 47...
Page 48: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 48...
Page 49: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 49...
Page 50: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 50...
Page 51: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 51...