TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
8
[H]
OK
It includes input, confirm, save and similar functionality.
Used to enter menu in the main screen.
if kept pressed for a long time on the main screen password entry window will
open or switch to Level-1
[I]
Numeric
Keypad
Numbers 0-9.
Allows entry of values directly on forms.
Provides fast access by entering the number of rows in the list.
Table 2 - LED Indicators
Label
Name of LED
LED - Permanent Light
LED - Blinking Light
Color
[J]
FIRE
N/A
Indicates that the panel is in
alarm status (250 ms)
Red
[K]
Energy
Indicates that the system is
being supplied from any
source
N/A
Green
[L]
System
Activated
Indicates that there is no
problem in the peripherals that
will affect the full operation of
the system
N/A
Green
[M]
System Out-of
Service
Indicates that zones or devices
or outputs are disabled
N/A
Yellow
[N]
Test
Indicates that one or more
zones are in a test state
N/A
Yellow
[O]
Night Mode
Indicates that the system is in
night mode.
N/A
Yellow
[P]
Delay
Indicates that the output
delays are active.
N/A
Yellow
[R]
General Failure
Indicates that there is a
system error. (system error
lights up together with
associated LED)
Reveals that there is any error in
the system
Yellow
[S]
System Failure
Indicates that there is a
system error.
N/A
Yellow
[T]
Power Failure
N/A
Indicates that there is a
malfunction in the power supply
Yellow
[U]
Battery Failure
N/A
Indicates that there is a
malfunction in the battery
Yellow
[V]
Ground Fault
N/A
Indicates that there is a
malfunction in the ground
connection
Yellow
[Y]
Siren
Indicates that the siren is in
the disabled state
Indicates that there is a
malfunction in the siren
Yellow
[Z]
Loop
Indicates that the loop PCB is
disabled.
It shows errors related to the
loop PCB such as loss, open
circuit, short circuit.
Yellow
[Z1]
Network
Indicates the panel is included
in the network.
Displays the error status of the
network.
Yellow
LCD should be checked for more detailed error description of the LED indicators above,