TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
13
6.2.3
Level 3
All the authorizations and functionality with regard to the system (except scenario management) are made available
at this level. Users of this level are authorized persons trained to install and maintain the system.
In order to switch to Level-3, it is necessary to have Level-3 password in the first place. If the panel is being
configured for the first time, Level 3 password is the activation code at the same time.
In order to enter Level-
3, select "Menu » Enter " and enter the 4
-digit Level-3 password using the keypad.
If the password is correct, the message "Access level 3 active" will be displayed on the screen. If the password is
incorrect, the "Wrong Password!" warning will be displayed.
In order to exit from level-
3, select "Menu» Exit" or hold down the" OK "key for a lo
ng while are in the main screen.
The message "Access level 1 active" will be displayed on the screen when exiting.
Authorizations to which a level 2 user is entitled, is listed below. For schematic representation refer to
“9.3 Appendix
-
Menu / Figure 39 : L
evel 3 Menu Flow”
.
•
Level-2 authorizations,
•
Defining device parameters and label,
•
Defining zone parameters and label,
•
General delay parameters,
•
Zonal delay parameters,
•
Displaying panel values,
•
Panel parameters,
•
Date time settings,
•
Loop functions,
•
TdNET functions,
•
Users,
•
Service time setting,
•
TCP/IP settings.
6.2.4
Level 4
Level-4 can be entered via a special apparatus and software provided by the manufacturer. At this level the user can
access the memory where the program is located and reset the operational data of the field.
6.2.5
Level Timeout
If one enters a level and leaves it unattended in active status, and if there is no operation performed in the panel,
then panel will activate the timeout period and user level automatically switches to Level-1 during the time-out period
for security purposes.
Table 5 : Level Timeout Periods
User Level
Timeout Period
Level-2
6 minutes
Level-3
30 minutes
In order to restore user levels, the level-login procedure must be followed from the very beginning.
6.3
Configuration using the Computer
Establish the connection with the computer as shown in
“9.4 Appendix
-Level / Figure 40 : PC
Ethernet Connection”
and run the "Teknim Addressable Fire Detection System Configuration Software". Teknim recommends the use of
"Teknim Addressable Fire Detection System Configuration Software" in order to get the best result for the installation
of fire system.
Software users are authorized persons trained to install and maintain the system.
Advantages of using software: