TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
12
6
Configuration
This section contains information on the configuration and use of the fire detection system.
6.1
Panel Activation
Activation is a process that enables access to the programming menu for the first installation of the addressable fire
detection system. In order to perform this process, a 4-digit password activation code is required.
The activation code is the first password of the programming menu, and such password can be changed later.
Re-activation code must be generated for the forgotten programming password.
6.1.1
Activation process:
1.
Enter "000" on the panel. (Press "0" key 3 times)
2.
In the window displayed, type the 4-digit activation code you have created after seeing the "Enter
password:" command and see the information that the panel is activated on the screen.
6.1.2
Generation of the activation code:
1.
Visit b2b.bilgibayim.com web address and login to the system with dealer user name and password.
2.
Enter the panel activation menu and generate a new activation code for the panel you want to activate by
entering the desired information in the form that opens.
6.2
User Levels
Some features of the panel are restricted by user levels and there are 4 user levels in the panel.
6.2.1
Level 1
Level 1 is defined as the default user level with the most basic features. The panel will be offering "Level-1" if the
user is not logged in. Authorizations provided to a level 1 user is listed below. For schematic representation refer to
“9.3 Appendix
-Menu / Figure 37
: Level 1 Menu Flow”
.
•
Displaying alarm list,
•
Displaying error list,,
•
Displaying the alert list,
•
Displaying the disabled devices,
•
Displaying the unoccupied zones,
•
Displaying event log,
•
Test for LCD, Indicators and Buzzer,
•
Muting buzzer.
6.2.2
Level 2
A user enters "Level-2" with a level 2 password that may be defined by the level 3 user. Authorizations to which a
level 2 user is entitled, is listed below. For schematic representation refer to
“9.3 Appendix
-Menu / Figure 38 : Level
2 Menu Flow”.
•
Level-1 authorizations,
•
Night/Day/Auto mode function,
•
General delays On/Off function,
•
Deactivating and reactivating devices/zones/outputs,
•
Time setting,
•
Zone testing,
•
Device LED test,
•
Displaying alarm counter,
•
Displaying (contact) information regarding Technical service,
•
Displaying the device list.
In order to exit from the level-
2, select "Menu » Exit” or
keep pressing on the" ESC "key for a long while on the main
screen.