TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
15
Table 8 : Default Device Parameters
Device Parameters
Value
Type
--
Zone
1
Label
[Device xxx]
Night Sensitivity
High
Day Sensitivity
High
Disabled
No
Table 9 : Default Loop Parameters
Loop Parameters
Value
Label
[Loop xx]
Active
Yes (No, for 1-loop panels)
Disabled
No
Cabling
Class A
Table 10 : Default Zone Parameters
Zone Parameters
Value
Label
[Zone xx]
Disabled
No
Delay
General
Zonal Delay Period
0
Table 11 : Default Output Parameters
Output Parameters
Value
Disabled
No
6.4.1
Panel Configuration Sequence
The following steps should be followed for panel configuration.
1
Login to Level-3,
2
Panel clock and date settings,
3
Panel parameters setting,
4
General delay setting,
5
Zonal delay setting,
6
Addition of new devices,
7
Device parameters
8
Zone parameters
9
TdNET (Network) parameters
6.4.2
Login to Level-3
System administrator is required to first login to Level 3 in order to make configuration settings. For the procedure for
login to Level-3, refer to the topic
“6.2.3. Level 3”
.
6.4.3
Panel Clock and Date Settings
The proper setting of the panel clock and date ensures real-time traceability of the panel. Otherwise, event log
entries will not reflect the real-time events of the panel. It is also important to enter these values individually for each
day, "Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday" as the start and end times on a day-by-
day basis are the factors that determine the "Night/Day" mode of the panel. "Date, Time, Day Start and End Hours"
settings can be made through the time and date settings window. The following steps should be followed for panel
time and date settings.
1
First, go to the main screen and follow the instructions below,