TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
28
1
Go to the
“Menu » Disable » “Disabled Outputs” menu,
2
Select the required output from the list and change the status into “PASSIVE”,
3
Change the output status into “ACTIVE” if you want to reactivate the output.
Figure 24 - Disabled Sirens Window
7.3.4
Disabled Loops
Disabling the loop causes all devices that are connected the that loop, to be disabled. However, the loop card and the
panel motherboard continue to communicate with each other.
In order to disable a loop, switch to at least level 3, and then follow the steps below;
1
Go to
“Men
u
» Program
ming
»
Loop Functions
»
Loop Parameters
” men
u,
2
Change the option “Disable” into “Yes”
,
3
Then press the "ESC" key in order to complete the saving process,
4
Chan
ge the disable option into “No” if you want to reactivate the loop.
Figure 25 - Loop Parameters
7.4
Zone Test
Zone testing is a feature that is used to test the alarm functions of fire detection devices. In cases where the settings
depicted under topics of the
“6.4.4.7 Sirens Under Testing” and “6.4.4.8 Buzzer
under Testing”
are fulfilled, sirens or
buzzer sounds for 10 seconds for the zone positioned within the scope of every test alarm and thereafter the system
resets.
The zone test is automatically terminated after 1 hour in case of any possibility that the zone may have been
forgotten in the testing process.